Chapter 5 Operating SCU
2. Actual battery capacity
The monitoring module can approximately calculate the remaining battery capacity
in real time. Through configuration at the host, the remaining battery capacity can
be displayed in the mode of percentage, remaining Ah or remaining time, etc. The
default is the percentage.
During the normal BC/FC management, the monitoring module regards the rated
capacity as the capacity that each battery group can reach. When the battery
discharges, the monitoring module will calculate the battery remaining capacity
according to the discharge current, discharge time and the preset "battery
discharge curve". When the battery is being charged, the monitoring module will
calculate the real-time battery capacity according to the detected charge current,
charge time and preset "battery charge efficiency". If the calculated battery
remaining capacity is higher than the rated capacity, the monitoring module will
automatically change the calculated battery remaining capacity to the rated
capacity.
AC information page
There is no AC data acquisition board in ACTURA Flex 48330 Power System,so
the configuration of "AC Input" can only be set to "None".
BC prompt and temperature information page
If the monitoring module bans BC and no temperature sensor is configured, this
page will not be displayed.
The first line of the information page displays the BC prompts, which will be
different with different systems, including:
1. Prompt the time of next Cyclic Boost according to the battery state
2. If BC is going on, the "Charging" will be prompted
3. If BC is disabled, this row will be empty
System Power:
Cyc BC After:
Bat. Temp:
Amb. Temp:
ACTURA Flex 48330 Power System User Manual
23%
55h
25°C
5°C