Vertical / Horizontal Combination Termination; Vertical / Horizontal Combination Term. (5" X 8"); Vertical / Horizontal Combination Term. (8" X 6-5/8" Decreaser) - kozy heat DASSEL DSL-36 Installation And Operation Manual

Direct vent dassel
Table of Contents

Advertisement

VERTICAL & HORIZONTAL COMBINATION TERMINATIONS
MAXIMUM VERTICAL & HORIZONTAL
COMBINATION VENTING
90° ELBOW
20 FT
(6.10 m)
For each additional elbow used after the first elbow, 3 ft. (91
45° elbow used, 1-1/2 ft. (457 mm) must be subtracted from the maximum venting allowed.
NOTE: (2) 45° degree elbows may be used in place of (1) 90° elbow.
NOTE: Horizontal sections
require 1/4" (6 mm) rise for
every 12" (305 mm) of travel.
NOTE: Pages 27-28 have information
on restrictor installation in
conjunction with venting installation.
Page 49 has information on restrictor
recommendations depending on burner flame
appearance and instructions on installation after
venting is completed.
VENTING
5" x 8"
20 FT
(6.10 m)
TERMINATION CAP
MAXIMUM VERTICAL &HORIZONTAL
COMBINATION VENTING WITH
WITH 8" x 6-5/8" DECREASER
90° ELBOW
20 FT
(6.10 m)
4 mm) must be subtracted from the maximum venting allowed. For each
IMPORTANT: A WALL THIMBLE PASS-THRU
MUST BE USED ON ALL HORIZONTAL VENT RUNS.
IF USING A 8" x 6-5/8" DECREASER FOLLOW VENT
PIPE MANUFACTURER‟S INSTALLATION
INSTRUCTIONS FOR THEIR WALL THIMBLE.
Depending on your particular venting needs,
a Decreaser may be necessary to terminate
the venting system.
PAGE 30
(Vertical with Decreaser)
20 FT
(6.10 m)
TERMINATION CAP
8" x 6-5/8" DECREASER
6" (152 mm)
CAUTION: This gas
appliance must not be
connected to or joined with
any other chimney flue
serving another appliance.