Zone Type
Type 16
Fire w/Verification
Type 20: Arm-Stay
(BR RF devices only)
Type 21: Arm-Away
(BR RF devices only)
Type 22: Disarm
(BR RF devices only)
Type 23 *
No Alarm Response
* The system can still be armed when these zone types are in a faulted condition.
Zone Type
Type 24
Silent Burglary
Type 77
Keyswitch
Type 81
AAV Monitor Zone
Description
• Provides a fire alarm when zone is shorted, but only after alarm is
verified.
• System verifies alarm by resetting zones for 12 seconds after short is
detected. A subsequent short circuit within 90 seconds triggers fire
alarm.
• Provides a trouble response when zone is open.
• Arms the system in Stay mode when the zone is activated.
• Pushbutton units send user number to the central station when
arming/disarming.
• User number for button must be assigned.
• Arms the system in Away mode when the zone is activated.
• Pushbutton units send user number to the central station when
arming/disarming.
• User number for button must be assigned.
• Disarms the system when the zone is activated.
• User number for button must be assigned.
• Can be used on a zone when an output relay action is desired, but with
no accompanying alarm (e.g., lobby door access).
• Zone faults/restores are event logged.
Description
• Usually assigned to all sensors or contacts on windows and infrequently
used exterior doors where siren sounding is NOT desired for alarms.
• Provides an instant alarm, with NO audible indication at any keypad or
external sounder, if the zone is faulted when the system is armed in the
Away, Stay, Instant, or Maximum modes.
• A report is sent to the central station.
• Assign to zone wired to a keyswitch.
• Do not use devices assigned as input type "BR" with this zone type.
• Assign to zone connected to AAV module.
• Monitors 2-way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting
stops, except
for fire alarms, which immediately terminate the voice session and
cause
a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell
timeout
has not expired) and reports that were stopped are sent.