Installation and Setup Guide

4219/4229 Expansion Zones

1.
Connect each module to the control's keypad
terminals.
If power supervision is required, use the Trigger
Module terminals as described in the Aux
Power Supervision Connections paragraph
in the Wiring to Keypads section (page 2-3).
2.
Assign the module a device address of 08 using
its DIP switches. The device address determines
the zone numbers being used, as shown below.
Expander Module Addresses
Zones...
Device Address...
17-24
08
3.
Connect sensors to the module's loops.
4.
If using relays with the 4229, connect the
desired field wiring to the unit's relay contact
terminals.
RELAY
CONNECTOR
RLY
RLY
2
1
REED
(TAMPER)
RELAYS OFF
SWITCH
Figure 7. Wiring Connections, 4219 & 4229 (4229 shown)
2-10
RELAY
DIP SWITCH
2
FOR SETTING ADDRESS
AND ZONE "A" RESPONSE
RELAY
1
NO C NC
TAMPER JUMPER POSITION
4229 IN CABINET
(NOT TAMPER)
4229 REMOTE
(TAMPER PROTECTED)
1
2
4
6
3
5
ZONES
B
C
D
A
Notes
Supports up to 8 expansion zones (NO or
NC) using 4219/4229 Zone Expander
Modules as follows:
Use 1000 ohm end-of-line resistors at the
end of loops connected to the 4219/4229
modules. (End-of line resistors used on the
control terminals are 2000 ohms.)
Expansion zones have normal response
time (400–500 msec), except zone
connected to each module's loop "A," which
can be set for fast response (10–15 msec).
4229
EITHER OR BOTH CAN BE USED
4-PIN CONSOLE PLUG
4
3
2
TB1
1
8
9
7
10
11
12
TERMINATE EACH
PROGRAMMED ZONE
WITH 1000 OHM (1K)
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE
300 OHMS + EOL)
E
G
H
F
TERMINALS ON
CONTROL PANEL
TB2
GRN
DATA OUT (>)
4
TO CONTROL
BLK
3
(–) GROUND
RED
(+) 12VDC
2
DATA IN (<)
YEL
FROM
1
CONTROL
(TERM 6)
(TERM 4)
(TERM 5)
(TERM 7)
4229-002-V0