Table 3-7 Sensor Settings Field Descriptions - Proliphix NT10e Configuration Manual

Basic series network thermostat
Hide thumbs Also See for NT10e:
Table of Contents

Advertisement

CHAPTER 3: Configuring the Thermostat Using the TMI
Use

Table 3-7 Sensor Settings Field Descriptions

Field
Local Sensor
State
Sensor Averaging
Sensor Correction
Remote Sensor 1 and 2
Name
State
Sensor Type
3-36
Table 3-7
to complete the Sensor Settings page fields.
Basic Series Network Thermostat Configuration Guide, Release 3.0
Beta Draft Confidential
Description
Select Enable or Disable to indicate the state of the internal
thermostat thermal sensor. The internal thermal sensor may be
disabled if only remote sensing is desired.
Disable – The internal thermal sensor is disabled. No Local
Sensor value is displayed on the
(page
3-9).
Enable (default) – The internal thermal sensor is enabled.
Select Enable or Disable to indicate if the thermostat internal
thermal sensor should participate in the algebraic averaging of
either or both of the Remote Sensors if the
enabled. (See
Zone Temperature (page
Disable – The thermostat internal sensor is excluded from
the thermal averaging calculations.
Enable (default) – The internal thermal sensor participates
in the algebraic averaging. The Zone Temperature now
reflects the average temperature of the averaged
measurements.
Selects a value to adjust the sensor for calibration.
°
°
°
-5
F (-2.8
C) through +5
F (2.8
The default is 0.
Displays the Name (15 characters) for the external thermal
sensor #1/#2.
RS 1 / RS 2
The default is none.
Select Enable or Disable to indicate if the external thermal
sensor #1 is installed on the thermostat.
Disable (default) – A remote external thermal sensor is not
connected to the thermostat. No Remote Sensor #1 or #2
value is displayed on the
Enable – A remote external thermal sensor is connected to
the thermostat.
Select the remote sensor type, either thermistor or analog so that
the appropriate temperature translation table is used to calculate
the temperature value. (Consult the Proliphix web site for a list
of sensors available in either type.)
Thermistor (default) – Thermistor-based thermal sensors.
Analog – Analog-based thermal sensors.