Page 1
Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide Release 1.0 Part No. 600-03000-350, Rev. 1 July 2010...
Page 2
3 years for the IMT series thermostats from the date of purchase. Proliphix shall not be liable to honor the terms of this warranty if the product has been used in any other application other than that for which it was intended, or if it has been subjected to misuse, accidental damage, acts of God, modification, or improper installation procedures.
Page 3
Return Material Authorization (RMA) number. Products may be returned for credit, exchange, or service with a Proliphix RMA number and with proof of purchase. Enclose a note explaining the symptoms of the problem, stating the RMA number, and the name, address and phone number of the company or individual contact.
Page 4
Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
Page 5
Beta Draft Confidential Overview The Proliphix Internet Managed Thermostat (IMT) 350c/350w provides a rich set of innovative features including the ability to configure settings through a graphical interface either locally or from any remote location. The “c” model suffix thermostats can be connected to your network with a CAT5/CAT5E/CAT6 Ethernet cable, while the "w"...
Page 6
(Y1) would energize the air conditioner compressor and the fan together. Detailed installation instructions for the HPA can be found in the HPA Installation Guide. Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
Install the CAT5/CAT5E/CAT6 cabling from the wiring center to the thermostat installation site for model IMT350c. This is not required for the IMT350w model (802.11 b/g wireless). Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0...
CAT5/CAT5E/CAT6 cables and HVAC cables should be a minimum of one inch. Before you Begin If you are removing an existing thermostat, Proliphix recommends that you label each connection as you remove the wiring. You will use these same wires (and labels) when you connect the IMT.
IMT base plate terminals for Heat Pump HVAC. A Heat Pump configuration always has a wire used to control a reversing valve. Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
Page 10
Consult your HVAC installer about the RVS type for your heat pump. Provides stage 1 heat or cool depending on the activation of the RVS. Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
Page 11
HVAC System The wiring colors shown above are examples of commonly used colors and may differ depending on the HVAC wiring that is used. Note Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
Page 12
HVAC System The wiring colors shown above are examples of commonly used colors and may differ depending on the HVAC wiring that is used. Note Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
Configuring Remote Sensors The Proliphix thermostats provide two remote (external) sensor ports. The IMT supports Thermistor and contact closure sensing. (Go to www.proliphix.com for a complete list of supported sensors.) You must configure the two switches for each sensor to match the sensor category.
Page 14
Figure 4 and match the label number to the Proliphix base plate number for CAT5/CAT5E/CAT6 color coding. If the other end of the CAT5/CAT5E/CAT6 cable is connected to a Proliphix EPA-20/60 Ethernet Power Adapter, follow the wiring scheme for T568A. Note All wiring must conform to local codes and ordinances.
Page 16
If Heat Pump is a model which activates the reversing valve (B) for heat mode. If Heat Pump is a model which activates the reversing valve (O) for cool mode. Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
The power settings determine which HVAC power source (RH or RC) is configured to turn on each HVAC system (cool, heat, and fan). Most applications use only RH power. The Proliphix thermostat is shipped from the factory with the RH and RC jumpered together.
Page 18
Beta Draft Confidential Installing and Wiring the Thermostat The IMT350c can be powered from different sources presented on the following Ethernet CAT5/5E/CAT6 interface (see Figure A Power over Ethernet (PoE) source is an Ethernet router, switch, or mid-span device that complies with the 802.3af Power over Ethernet standard. (IMT350c...
Obtain the IMT350's IP address from the LCD interface. Enter the IP address into your browser. Log in using the default user name of "admin" and the password of "admin". Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...
Page 20
Beta Draft Confidential Logging In to the Thermostat Proliphix Internet Managed Thermostat (IMT) 350c/350w Installation Guide, Release 1.0 Part No. 600-03000-350, Rev. 1...