Installing The Sun Netra Cp3060 Blade Server - Sun Microsystems Netra CP3060 User Manual

Blade server
Table of Contents

Advertisement

7. Carefully align the edges of the card with the card guides in the appropriate
slot.
It might be helpful to look into the enclosure to verify correct alignment of the
rails in the guides.
8. Taking care to keep the blade server aligned in the guides, slide the card in
until the injector/ejector latches engage the card cage.
9. Push the blade server into the midplane connectors and close the latches to seat
the blade server in the connectors.
10. Tighten the locking screws to ensure that the blade server is secured into the
shelf.
11. Install the Sun Netra CP3060 blade server into the shelf.
Go to
for those instructions.
2.5.2

Installing the Sun Netra CP3060 Blade Server

1. If you have installed a Sun Netra CP3060 RTM, go to the front of the system
and locate the card slot where you installed the RTM at the rear of the system.
2. Remove the filler panel, if necessary.
The filler panel is secured to the card cage using two screws, one at the top of the
filler panel, the other at the bottom. Store the filler panel in a safe place; you
might need to use it again if you have to remove a card for an extended period of
time.
3. Prepare the blade server by opening the injector/ejector latches (
4. Carefully align the edges of the blade server with the card guides in the
appropriate slot (
It might be helpful to look into the enclosure to verify correct alignment of the
rails in the guides.
5. Taking care to keep the blade server aligned in the guides, slide the blade
server in until the injector/ejector latches engage the card cage.
2-14
Netra CP3060 Board User's Guide • April 2009
Section 2.5.2, "Installing the Sun Netra CP3060 Blade Server" on page 2-15
FIGURE 2-7
).
).
FIGURE 2-6