7 Commissioning
7.3

Gas settings

Tab.24
Factory setting G20 (H gas)
Parameter
Description
Maximum speed for central heating
Minimum speed for central heating
Start speed
Restrictor
ø (mm)
Fig.28
Replacing restrictor
Tab.25
Adjustment for gas type G31 (propane)
Parameter
Description
Maximum speed for central heating
Minimum speed for central heating
Start speed
Restrictor
ø (mm)
42
The meaning of the error codes can be found in the error table.
7.3.1

Adaptation to a different gas type

Warning
Only a qualified installer may carry out the following operations.
Before operating with a different type of gas, carry out the following steps.
1. Check the correct diameter of the existing restrictor (see table) and
replace it if necessary.
2. Set the fan speed as indicated in the table for the relevant gas type.
The speed can be changed with a parameter setting.
AD-3000112-01
3. Check the setting of the gas/air ratio.
7.3.2

Checking/setting the combustion

1. Unscrew the cap from the flue gas measuring point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
Warning
During measurement, seal the opening around the sensor fully.
Important
The flue gas analyser must have a minimum accuracy of
±0.25% O
The flue gas analyser must meet the requirements of BS 7927
or BS-EN 503793 and be calibrated according to the manufac­
turer's requirements.
3. Measure the percentage of O
urements at full load and at part load.
210-80
210-120
51
64
12
13
17
17
8,4
8,4
210-80
210-120
52
61
15
14
20
20
6,5
6,5
/CO
.
2
2
/CO
in the flue gases. Take meas­
2
2
210-160
210-200
48
57
10
12
17
17
210-160
210-200
60
55
15
13
22
22
10
10
114494 - v.05 - 06022018