Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
Single Module UPS with integral battery, optional battery cabinet, and optional options cabinet • Single Module UPS with remote battery • Single Module UPS with remote battery and optional options cabinet Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system—the UPS modules, battery strings and options or accessories installed. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
Battery maintenance or battery replacement should be performed only by authorized service personnel. • Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation xvii 164201300 Rev. N 013004...
System; ; provides procedures for operating the Parallel System, and information about maintenance and responding to system events. Contact your local Powerware Field Service office for information on how to obtain copies of this manual. Getting Help If you need to schedule initial startup, need regional locations and telephone numbers,...
The operating environment must meet the weight, airflow, size and clearance, requirements specified in Appendix A. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 1--1 164201300 Rev. N 013004...
For external wiring requirements, including the minimum AWG size of external wiring, refer to Tables A through F in Appendix A for the Powerware 9330 (10 kVA---20 kVA) UPS or Tables G through M in Appendix A for the Powerware 9330 (25 kVA---40 kVA) UPS.
The UPS and accessory cabinets are shipped bolted to wooden pallets, as shown in Figures 1---1 or 1---2, and protected with outer protective packaging material. Figure 1 ---1. Powerware 9330 (10 kVA ---20 kVA) UPS Cabinet as Shipped on Pallet Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 1--3...
Page 24
Figure 1 ---2. Powerware 9330 (25 kVA ---40 kVA) UPS Cabinet as Shipped on Pallet Carefully inspect the outer packaging for evidence of damage during transit. CAUTION: Do not install a damaged cabinet. Report any damage to the carrier and contact your local sales or service office immediately.
Page 25
After removing the protective covering, inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact the Powerware, Inc. Customer Service Department immediately to determine the extent of the damage and its impact upon further installation.
Page 26
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 1--6 164201300 Rev. N 013004...
Details about control wiring are provided in each procedure for connecting options and features. Drawing 164201300---2 and Tables X and Y in Appendix A identify the control wiring terminations. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--1 164201300 Rev. N 013004...
Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue rolling the cabinet down the pallet until the cabinet is clear of the pallet. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--2 164201300 Rev. N 013004...
Page 29
PALLET SOLID FRONT PANEL SHIPPING BOLTS (1) FRONT SHIPPING BRACKET (3) FRONT VIEW Figure 2 ---1. Removing Front Shipping Bracket (Powerware 9330 (10 kVA ---20 kVA)) Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--3 164201300 Rev. N 013004...
Use a forklift or other material handling equipment to move the cabinet to the installation area. Insert the forklift jacks between the skids on the bottom of the unit. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--5 164201300 Rev. N 013004...
Page 32
14. Secure the Options cabinet in position by lowering the leveling feet, until cabinet is not resting on the casters and the cabinet is level. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--6 164201300 Rev. N 013004...
Page 33
BOLTS (2) SHIPPING BOLTS (1) FRONT SHIPPING BRACKET (3) FRONT VIEW Figure 2 ---3. Removing Options Cabinet Front Shipping Bracket (Powerware 9330 (10 kVA ---20 kVA)) Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--7 164201300 Rev. N 013004...
Do not remove bolts (2) securing the bracket to the cabinet. Remove four bolts, (4) in Figure 2---6, securing removable skid (5) and remove skid. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--9 164201300 Rev. N 013004...
Page 36
PALLET SOLID FRONT PANEL FRONT SHIPPING SHIPPING BOLTS (1) BRACKET (3) FRONT VIEW Figure 2 ---5. Removing Front Shipping Bracket (Powerware 9330 (25 kVA ---40 kVA)) Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--10 164201300 Rev. N 013004...
Page 38
Install Battery cabinets and Options cabinet, by repeating steps 1 through 10 for remaining cabinets and then proceed to paragraph 2.3 for Battery cabinet installation and paragraph 2.4 for Options cabinet installation. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--12 164201300 Rev. N 013004...
Power Wiring If not already removed, remove left front solid panel and right front vented panel from the Powerware 9330 (10 kVA---20 kVA) UPS cabinet or left front solid panel and front vented panels from the Powerware 9330 (25 kVA---40 kVA) UPS cabinet.
Page 40
Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. Note wiring connections for dual feed systems. NOTE: If connecting the UPS to a Parallel Cabinet, refer to Powerware 9330 Parallel Cabinet Installation and Operation manual referenced in the Introduction to this manual.
Reinstall Customer Interface conduit landing plate. Refer to Chapter 4 for installation instructions. When wiring is complete, secure UPS by reinstalling all panels removed in previous steps. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--15 164201300 Rev. N 013004...
Roll the Battery cabinet to a spot near the right side of the UPS. Remove left front solid panel, and right front vented panel from the Powerware 9330 (10 kVA---20 kVA) UPS cabinet or left front solid panel and front vented panels from Powerware 9330 (25 kVA---40 kVA) UPS cabinet. Front panels are secured with magnetic latches and are removed by pulling panels straight forward to disengage magnetic latches (see Figure 2---1 or 2---5).
Page 47
To join additional battery cabinets, perform the following steps. Refer to Figure 2---7 for non-permanent installation or Figure 2---8 for permanent installation of the Powerware 9330 (10 kVA---20 kVA) UPS and Figure 2---9 for non-permanent installation or Figure 2---10 for permanent installation of the Powerware 9330 (25 kVA---40 kVA) UPS.
Page 48
When all wiring is complete, proceed to Chapter 3 and connect battery strings in accordance with instructions contained in paragraph 3.4.2. Repeat steps 1 through 21 to join additional Battery cabinets. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--22 164201300 Rev. N 013004...
Roll the Options cabinet to a spot near the left side of the UPS. Remove left front solid panel, and right front vented panel from the Powerware 9330 (10 kVA---20 kVA) UPS cabinet or left front solid panel and front vented panels from Powerware 9330 (25 kVA---40 kVA) UPS cabinet. Front panels are secured with magnetic latches and are removed by pulling panels straight forward to disengage magnetic latches (see Figure 2---1 or 2---5).
Page 50
OPTIONAL DISTRIBUTION HOUSING Figure 2 ---11. Options Cabinet Installation --- Powerware 9330 (10 kVA ---20 kVA) (Non–Permanent Mounting) Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--24 164201300 Rev. N 013004...
Page 51
OPTIONAL DISTRIBUTION HOUSING Figure 2 ---12. Options Cabinet Installation --- Powerware 9330 (10 kVA ---20 kVA) (Permanent Mounting) Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--25 164201300 Rev. N 013004...
Battery Power Wiring If not already removed, remove left front solid panel and right front vented panel from the Powerware 9330 (10 kVA---20 kVA) UPS cabinet or left front solid panel and front vented panels from the Powerware 9330 (25 kVA---40 kVA) UPS cabinet.
Page 55
Refer to Appendix A of this manual for wiring and termination requirements and wiring access information. Secure the UPS by reinstalling safety shield panels, front vented panels, and front solid panel. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--29 164201300 Rev. N 013004...
Proceed to step 25. If wiring a single feed system, proceed to step 11; if wiring a dual feed system, proceed to step 13. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--30 164201300 Rev. N 013004...
Page 57
Install Square-D Type QO or QOB breakers into PDM panelboard. Refer to Appendix A of this manual for access information. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--31 164201300 Rev. N 013004...
Installation Checklist to be sure you have completed all applicable equipment installation. NOTE: The Installation Checklist MUST be completed prior to starting the UPS system for the first time. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--32 164201300 Rev. N 013004...
UPS cabinet. Summary alarms and/or building alarms are wired appropriately. (OPTIONAL) Startup and operational checks performed by authorized service personnel. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 2--33 164201300 Rev. N 013004...
Suivre les précautions qui s’imposent. • Pour le remplacement, utiliser le même nombre et modéle des batteries. • L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 3--1 164201300 Rev. N 013004...
Ensure that battery breaker CB2 is in the OFF position. If not, set breaker to OFF position. Remove left front solid panel and right front vented panel from Powerware 9330 (10 kVA---20 kVA) UPS or left front solid panel and front vented panels from Powerware 9330 (25 kVA---40 kVA) UPS.
Page 63
Figure 3 ---1. Battery Schematic --- Powerware 9330 (10 kVA ---20 kVA) UPS and Battery Cabinet Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 3--3 164201300 Rev. N 013004...
Page 64
Figure 3 ---2. Battery Schematic --- Powerware 9330 (25 kVA ---40 kVA) UPS Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 3--4 164201300 Rev. N 013004...
Ensure that battery breaker CB2 is in the OFF position. If not, set breaker to OFF position. Remove left front solid panel and right front vented panel from Powerware 9330 (10 kVA---20 kVA) UPS or left front solid panel and front vented panels from Powerware 9330 (25 kVA---40 kVA) UPS.
Secure the Battery Cabinet by reinstalling safety shield panel, and front vented panel. If you are installing more than one battery cabinet, perform Steps 1 through 6 for each cabinet. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 3--6 164201300 Rev. N 013004...
Page 67
CONNECT CONNECT RED TO RED TO BLACK BLACK BLACK CONNECTOR CONNECT RED TO BLACK CONNECTOR BATTERY STRINGS Figure 3 ---3. Battery String Connection Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 3--7 164201300 Rev. N 013004...
Install battery system in accordance with battery and rack manufactures instructions. Install DC disconnect device between battery system and UPS Cabinet. Connect battery system to UPS cabinets (refer to Paragraph 2.2.4 or 2.4.3). Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 3--8 164201300 Rev. N 013004...
Securely mount the Remote EPO switch enclosure bottom. Recommended locations include operator’s consoles or by exit doors. Refer to Appendix A, Drawing 164201300---18, for enclosure dimensions and wiring knockouts. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 4--1 164201300 Rev. N 013004...
Page 70
Connect the Remote EPO wiring as shown in Tables 4---1 and 4---2 and Figure 4---2. If you are installing multiple Remote EPO stations, wire additional stations in series with the first Remote EPO. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 4--2 164201300 Rev. N 013004...
Page 71
When wiring is complete, remove cover from Remote EPO switch enclosure bottom. Turn cover over and secure to enclosure bottom. Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 4--3 164201300 Rev. N 013004...
Page 72
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 4--4 164201300 Rev. N 013004...
RMP still does not operate correctly, replace the fuse. If this does not correct the problem, contact your local field service office for verification that the RMP is working correctly. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 5--2 164201300 Rev. N 013004...
Page 75
CUSTOMER. THE MAXIMUM DISTANCE BETWEEN THE REMOTE MONITOR AND THE UPS IS NOT TO EXCEED 500 FEET. Figure 5 ---3. Remote Monitor Panel (RMP) --- Top Internal View Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 5--3 164201300 Rev. N 013004...
Page 76
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 5--4 164201300 Rev. N 013004...
IRC still does not operate correctly, replace the fuse. If this does not correct the problem, contact your local field service office for verification that the IRC is working correctly. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 6--2 164201300 Rev. N 013004...
Page 79
Section II Operation Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
Page 80
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
Operation Looking Inside the UPS System The Powerware 9330 is a continuous duty, solid-state, transformerless (at 208/220 VAC), three phase, true online system that provide conditioned and uninterruptible AC power to the UPS systems output. The UPS supports process control, data processing, telecommunications/PBX, research, and non---patient medical equipment.
Page 82
Power Processsing Unit (PPU) for servicing, while still suppling power to the critical load. The operation of the UPS system is described in greater detail in the following paragraphs. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--2 164201300 Rev. N 013004...
System events, alarm horns, and indicator lights are described in Chapter 12, “Responding to System Events.” The following descriptions provide the differences in UPS operating modes. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--3 164201300 Rev. N 013004...
The battery is not charged directly from the unregulated rectifier. Instead, a separate battery charger is used to maintain the proper charge level on the battery during normal operation. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--4 164201300 Rev. N 013004...
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--5...
The static switch is wired in series with the back feed protection contactor and together they are wired in parallel with Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--6 164201300 Rev. N 013004...
Page 87
Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--7 164201300 Rev. N 013004...
High Efficiency mode is a normal operating mode, and not an alarm condition. While the UPS is in High Efficiency mode, the NORMAL light on the front display will illuminate. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--8 164201300 Rev. N 013004...
The UPS will remain in this operating mode until the input power to the rectifier is again within the specified voltage or frequency acceptance windows. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--9 164201300 Rev. N 013004...
Page 90
The greater the load, the less support time the battery will have. Decrease the load, and the battery support time will generally increase. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--10 164201300 Rev. N 013004...
CHARGER Main Power Flow Breakers Contactors Trickle Current Closed Energized Open De- -Energized BATTERY Figure 7 ---6. Path of Current Through the UPS in Test Mode Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--11 164201300 Rev. N 013004...
DC IN Bus. The raw DC at this point will be approximately 290 VDC. A precharge system precharges the DC IN Bus prior to the input contactor being closed. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--12 164201300 Rev. N 013004...
External Batteries connect in parallel to the Internal Battery via an internal breaker. The internal charger charges the Batteries in parallel or in conjunction with an optional external charger Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--13 164201300 Rev. N 013004...
Page 94
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 7--14 164201300 Rev. N 013004...
Figure 8---1 identifies and shows the location of the controls and indicators on the Powerware 9330 (10 kVA---20 kVA) UPS and Figure 8---2 identifies and shows the location of the controls and indicators on the Powerware 9330 (25 kVA---40 kVA) UPS.
Page 96
SWITCH AC INPUT BREAKER CB1 MAINTENANCE BYPASS SWITCH OPTIONS BATTERY CABINET CABINET CABINET Figure 8 ---1. Powerware 9330 (10 kVA ---20 kVA) UPS Controls and Indicators 8--2 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
A Cold Start switch is provided to start the UPS in Battery Mode when no commercial power is available. The Cold Start Switch is described in detail in Chapter 9, “UPS Operating Instructions.” 8--4 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
8.3.6 Auto Restart An Auto Restart function can be enabled to automatically restart the UPS after a power outage. To have the Auto Restart function enabled, contact a Powerware service representative. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 8--5 164201300 Rev.
An optional 208/208 or 208/480 VAC output isolation transformer provides an isolated output to the critical load or for applications that require 480 VAC. The transformer is contained in the separate options cabinet. 8--6 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
Up to four optional X-Slot cards can be installed in the UPS module at any time. The X-Slot cards support several protocols such as SNMP , HTTP , AS-400, and Modbus ® See Chapter 13, “Communications” for additional information. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 8--7 164201300 Rev. N 013004...
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. • Always conform to the more detailed safety precautions described in “Important Safety Instructions” section of Chapter 14. 8--8 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
Stop and refer to the Operator’s Manual for more information. RISK OF ELECTRIC SHOCK There is a risk of electric shock present, and you should observe associated warnings. The UPS contains high voltages. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 8--9 164201300 Rev. N 013004...
Page 104
This Page Intentionally Left Blank. 8--10 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 164201300 Rev. N 013004...
(5), and a vertical column of backlit status indicators, (6). The following sections describe using the UPS Control Panel to monitor the UPS. Refer to Chapter 10 UPS Operating Instructions for use of the operational controls. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--1 164201300 Rev. N 013004...
Look at a log of UPS events (alarms, notices, and commands) (see paragraph 9.3.2). After approximately one hour, the display screen dims. To restore the screen, press any pushbutton once. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--2 164201300 Rev. N 013004...
ALARM: AC INPUT UNDER VOLTAGE CMD: LOAD OFF COMMAND CMD: NORMAL MODE COMMAND 06/20/2003 10:20:03.539 EVENTS SHOW ALL Figure 9 ---4. Event Simple History Log Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--4 164201300 Rev. N 013004...
ACTIVE EVENTS ALARM: AC INPUT UNDERVOLTAGE ALARM: BYPASS UNDER VOLTAGE NOTICE: BATTERY VOLTAGE LOW NOTICE: NO SYNC ON HISTORY Figure 9 ---6. Active System Events Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--5 164201300 Rev. N 013004...
The Input screen shows the phase-to-phase voltage, phase current, and frequency, of the incoming utility, followed by the KVA, KW, and power factor measurements. INPUT FREQ SYSTEM Figure 9 ---7. Input Meter Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--6 164201300 Rev. N 013004...
Page 111
Figure 9 ---8. Output Meter Screen The Bypass screen shows the phase-to-neutral voltage, and frequency of the bypass source. BYPASS Freq SYSTEM Figure 9 ---9. Bypass Meter Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--7 164201300 Rev. N 013004...
Page 112
The Output Current Screen displays a real-time bar graph of the output current of the UPS. The graph shows the current for each phase. Output I 125% 100% Figure 9 ---11. Output Current (Load) Meter Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--8 164201300 Rev. N 013004...
The Input screen shows the phase-to-phase voltage, phase current, and frequency, of the incoming utility, followed by the KVA, KW, and power factor measurements. SYSTEM INPUT FREQ UNIT Figure 9 ---12. System Input Meter Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--9 164201300 Rev. N 013004...
Page 114
Figure 9 ---13. System Output Meter Screen The Bypass screen shows the phase-to-neutral voltage, and frequency of the bypass source. BYPASS Freq UNIT Figure 9 ---14. System Bypass Meter Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--10 164201300 Rev. N 013004...
LCD screen. To return to the System Setup menu screen, select the pushbutton. CONTRAST ADJUST Figure 9 ---16. Contrast Adjust Menu Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--11 164201300 Rev. N 013004...
Page 116
UPS unit. Figure 9---18 shows the Unit Type screen. To return to the System Setup menu screen, select the pushbutton. UNIT TYPE MODEL: POWERWARE 9330 CTO: 000000000000000 SERIAL: 0000000000000000 Figure 9 ---18. Unit Type Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--12 164201300 Rev. N 013004...
ENTER pushbutton. The System Setup Level 1 menu screen is displayed. The default password is L1. ENTER PASSWORD IF NO PASSWORD THEN PRESS ENTER ENTER Figure 9 ---19. Enter Password Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--13 164201300 Rev. N 013004...
Once the new password is entered, select the pushbutton. The Change Password Save screen is displayed. CHANGE PASSWORD OLD: NEW: Figure 9 ---21. Change Password Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--15 164201300 Rev. N 013004...
Page 120
SELECT pushbutton. CHANGE PASSWORD OLD: NEW: SAVE ABORT RETRY SELECT Figure 9 ---22. Change Password Save Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--16 164201300 Rev. N 013004...
Page 121
To complete the save function and return to the Setup Menu screen, select the pushbutton. DATE & TIME DAY DT MONTH YEAR HOUR MINUTE SAVE 2000 Figure 9 ---23. Date & Time Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--17 164201300 Rev. N 013004...
Page 122
To complete the save function and return to the Setup Menu screen, select the pushbutton. SERIAL PORTS PORT BAUD PARITY DATA STOP SAVE COM1 9600 NONE Figure 9 ---24. Port Setup Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--18 164201300 Rev. N 013004...
PPU ON TOGGLES BETWEEN TOGGLES BETWEEN HI-EFF AND NORMAL, ONLINE AND HI-EFF, DEPENDING ON MODE DEPENDING ON MODE Figure 9 ---25. System Controls Screen in Normal Mode Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--19 164201300 Rev. N 013004...
Page 124
TOGGLES BETWEEN TOGGLES BETWEEN NORMAL AND HI-EFF, HI-EFF AND ONLINE, DEPENDING ON MODE DEPENDING ON MODE Figure 9 ---26. System Controls Screen in High Efficiency Mode Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--20 164201300 Rev. N 013004...
ON after an outage. The charger must then be set to OFF manually. CHARGER CONTROLS CHARGER ON CHARGER OFF Figure 9 ---27. Charger Controls Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--21 164201300 Rev. N 013004...
Chapter 10, “UPS Operating Instructions”. UNIT SHUTDOWN THIS WILL REMOVE POWER TO THE LOAD! ARE YOU SURE? HOLD YES FOR 2 SECONDS TO POWER DOWN Figure 9 ---28. Shutdown Screen Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--22 164201300 Rev. N 013004...
The Alarm indicator may be lit along with other indicators. For more information about audible horns, refer to the “System Event Horns” section of Chapter 12. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--23 164201300 Rev. N 013004...
Page 128
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 9--24 164201300 Rev. N 013004...
On the UPS, close Battery breaker CB2. NOTE: If Auto Restart is enabled, UPS will automatically start in approximately one minute. If installed, close the Battery breakers on Battery cabinets. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--1 164201300 Rev. N 013004...
The critical load is immediately supplied by the bypass source, in Bypass mode. The UPS is now operating in the bypass mode and the BYPASS status indicator is illuminated. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--2 164201300 Rev. N 013004...
Normal mode and supply the critical load. The UPS is now operating in the Bypass mode and the BYPASS status indicator is illuminated. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--3 164201300 Rev. N 013004...
Select NORMAL or HI -- EFF from the System Control menu. Normal Mode Requested appears on the screen. The status indicator on the UPS Control Panel indicates the UPS is in Normal---Battery mode. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--4 164201300 Rev. N 013004...
The PPU status indicates READY. System is now on bypass and UPS power processor remains on. WARNING: Power is present inside the UPS and Options cabinets. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--5 164201300 Rev. N 013004...
The UPS is now operating in the Normal mode and the NORMAL status indicator is illuminated. The PPU status indicates ONLINE. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--6 164201300 Rev. N 013004...
The input, output, battery and bypass backfeed contactors open and the PPU is turned off. The maintenance bypass source supplies the critical load. WARNING: Power is present inside the UPS and Options cabinets Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--7 164201300 Rev. N 013004...
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure, in paragraphs 10.2 or 10.3. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--8 164201300 Rev. N 013004...
NOTE: The following instructions are for the Powerware supplied REPO switch. If a customer supplied REPO switch is used it may not activate in the same manner.
Page 138
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 10--10 164201300 Rev. N 013004...
UPS. This feature is useful if the UPS is located in a remote area where the UPS alarm horn may not be heard immediately. CAUTION: Contacts should not be operated in excess of 120 VAC @ 5A maximum. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 11--1 164201300 Rev. N 013004...
The NORMAL indicator is also lit. After 30 seconds of run time, the alarm indicator will illuminate and a horn sound. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 11--2 164201300 Rev. N 013004...
Page 141
The UPS battery backup is supplying the critical load. The utility power is either interrupted or out of specification. • ALARM MODE The UPS system is issuing an alarm that affect the current UPS mode Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 11--3 164201300 Rev. N 013004...
Page 142
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 11--4 164201300 Rev. N 013004...
(For descriptions of the status indicators, refer to paragraph 9.6 “Reading the Status Indicators” of Chapter 9.) Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--1 164201300 Rev. N 013004...
HA Condition Cleared Check CSB Setup HA Service Required Check CSB Setup OK HA Condition Cleared Check Inverter HA Service Required Check Inverter OK HA Condition Cleared Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--2 164201300 Rev. N 013004...
Page 145
HA Service Required Gate Driver Failed 1 OK HA Condition Cleared Heat Sink Thermistor Failure HA Service Required Heat Sink Thermistor Failure OK HA Condition Cleared Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--3 164201300 Rev. N 013004...
Page 146
HA Condition Cleared Output Phase Rotation HA User Action Required Output Phase Rotation OK HA Condition Cleared Parallel Setup Error Service Required Parallel Setup Error OK Condition Cleared Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--4 164201300 Rev. N 013004...
Page 147
Warning: Battery Time is Low OK HA Condition Cleared Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--5 164201300 Rev. N 013004...
Page 148
HA Information Only Call Phone # 4 Clear HA Condition Cleared Calling Unsuccessful Information Only Calling Phone #1 HA Information Only Calling Phone #1 OK HA Condition Cleared Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--6 164201300 Rev. N 013004...
Page 149
Information Only Phone #3 Failed Information Only Phone #4 Failed Information Only SBM IO 1 Not Reporting Information Only SBM IO Not Reporting OK Condition Cleared Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--7 164201300 Rev. N 013004...
Page 150
Condition Cleared System Not Redundant Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--8 164201300 Rev. N 013004...
Page 151
UPS Power Supply OK HA Service Status Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--9 164201300 Rev. N 013004...
Page 152
Normal Mode PPU On PPU Off Table Key To Log Column HA --- Event recorded in History and Active Logs. --- Event recorded in Active Log only. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 12--10 164201300 Rev. N 013004...
UPS should be male. Figure 13---1 shows the pin assignments for Serial Port, and Table 13---1 describes them. For connection and set up of a Modem, please contact Powerware. See “Getting Help” in the “Introduction” of this manual for contact information.
The serial port is pre-configured and can not be changed. 13.4 X-Slot Cards The Powerware 9330 contains a factory-installed X-Slot communication bay (refer to Appendix A, Drawings 164201300---8 or 164201300---9 for bay location), and is compatible with the following optional cards (see Figure 13---2): •...
Single-Port Card --- connects to the Powerware Expansion Chassis to enable multiple communication options. For installation and set up of an X-Slot card, please contact Powerware. See “Getting Help” in the “Introduction” of this manual for contact information. Refer to the manual supplied with the X-Slot card for user instructions.
Control Panel softkeys. Refer to Chapter 9 “Using the Control Panel” for instructions on navigating the control panel. Figures 13---3 through 13---18 show typical screens using this function. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--4 164201300 Rev. N 013004...
Page 157
Figure 13 ---3. Main Screen --- UPS Normal Mimic Figure 13 ---4. Main Screen --- UPS On Battery Mimic Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--5 164201300 Rev. N 013004...
Page 158
Figure 13 ---5. Main Screen --- UPS On Bypass Mimic Figure 13 ---6. System Controls Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--6 164201300 Rev. N 013004...
Page 159
Figure 13 ---7. Load Off Figure 13 ---8. Events --- History Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--7 164201300 Rev. N 013004...
Page 160
Figure 13 ---9. Events --- Active Figure 13 ---10. Input Meter Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--8 164201300 Rev. N 013004...
Page 161
Figure 13 ---11. Output Meter Figure 13 ---12. Bypass Meter Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--9 164201300 Rev. N 013004...
Page 162
Figure 13 ---13. Output Current (Load) Meter Figure 13 ---14. Setup Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--10 164201300 Rev. N 013004...
Page 163
Figure 13 ---15. Contrast Adjust Figure 13 ---16. Date and Time Setup Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--11 164201300 Rev. N 013004...
Page 164
Figure 13 ---17. Serial Port Setup Figure 13 ---18. Versions Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--12 164201300 Rev. N 013004...
Esc+H Prints the entire log with a firmware version header To use a key combination, hold down the Esc key and press the letter key. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--13 164201300 Rev. N 013004...
Page 166
08/12/2000 14:17:23.606 ALARM: Rectifier Under Voltage OK 08/12/2000 14:17:25.557 ALARM: Battery Under Voltage OK 08/12/2000 14:19:01.899 CMD: PPU On Command 08/12/2000 14:19:04.089 STATUS: K1 (Input) Closed Figure 13 ---19. Event History Log Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 13--14 164201300 Rev. N 013004...
If the string requires service, refer to the battery manufacturer’s operating manual for instructions on battery maintenance, or contact your local field service office. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 14--1 164201300 Rev. N 013004...
Page 168
Suivre les précautions qui s’imposent. • Pour le remplacement, utiliser le même nombre et modéle des batteries. • L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 14--2 164201300 Rev. N 013004...
Monitor system parameters as described in Chapter 9, “Using the Control Panel.” The UPS cooling air intake filter on the Powerware 9330 (10 kVA---20kVA) is located behind the removable front panel. The UPS cooling air intake filters on the Powerware 9330 (25 kVA---40kVA) are located behind both removable front panels.
14.4 Maintenance Training A basic training course, available from Powerware, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Powerware Training Coordinator in Raleigh, North Carolina, or call Powerware field service at 1 -- 800 -- 843 -- 9433.
Power Factor Minimum 0.96 Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4 Battery Voltage 288 VDC nominal (144 cells @2V/cell) Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 15--1 164201300 Rev. N 013004...
1 Hz per second maximum (adjustable) Overload Capability 1101---125% for 10 minutes 1126---150% for 1 minute Maximum Output Capability 300% peak for 10 cycles without bypass Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 15--2 164201300 Rev. N 013004...
Electrostatic Discharge (ESD) Meets IEC 801---2 specifications. Withstands up Immunity to 25 kV pulse without damage and with no disturbance or adverse effect to the critical load. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 15--3 164201300 Rev. N 013004...
Page 174
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation 15--4 164201300 Rev. N 013004...
Minimum conductor size (number per ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201300---6 164201300---1 2 of 17 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---3 164201300 Rev. N 013004...
Page 178
20/20 20/14 19.2 DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201300---6 164201300---1 3 of 17 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---4 164201300 Rev. N 013004...
Page 179
3 , 1 Neutral, 1 gnd DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201300---6 164201300---1 4 of 17 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---5 164201300 Rev. N 013004...
Page 180
Minimum conductor size (number per ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201300---6 164201300---1 5 of 17 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---6 164201300 Rev. N 013004...
Page 181
Minimum conductor size (number per ) DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201300---6 164201300---1 6 of 17 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---7 164201300 Rev. N 013004...
Page 182
40/40 40/28 33.5 DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: map to drawing #164201300---6 164201300---1 7 of 17 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---8 164201300 Rev. N 013004...
Page 183
40/28 208/220 208/220 DESCRIPTION: POWER WIRING INSTALLATION NOTES NOTE: Callout letter DRAWING NO: SHEET: 164201300---1 8 of 17 map to drawing #164201300---6 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---9 164201300 Rev. N 013004...
Page 184
Tables R through U for conduit requirements. Drawings 164201300---8 through 164201300---12 show the location of the power cable terminals inside the UPS, Options, and Battery Cabinets. Table N. UPS Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA) Size of Pressure Tightening Torque...
Page 185
Table O. UPS Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA) Size of Pressure Tightening Torque Type Termination N-M (lb-in.) Screw Terminal Function Terminal Function 13.5 (120) AC Input to UPS Phase A 1 --- #14---2/0 3/16 in. Hex...
Page 186
Table P. Options Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA) Size of Pressure Tightening Torque Type Termination N-M (lb-in.) Screw Terminal Function Terminal Function AC Input to UPS Phase A 1 --- #14---#2 #2 --- 5.6 (50) Rectifier Transformer...
Page 187
R. All 9330 products can accommodate a double size neutral. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.
Page 188
Table S. Power Cable Conduit Requirements Powerware 9330 (20 kVA) Minimum Number of Powerware Conduit Number of Voltage Terminal Wires in Trade Size System Conduits Conduit (inches) AC Input to UPS (A, B, C, Gnd) 208/220 AC Input to Bypass...
Page 189
Table T. Power Cable Conduit Requirements Powerware 9330 (25 kVA -- 30 kVA) Minimum Number of Powerware Conduit Number of Voltage Terminal Wires in Trade Size System Conduits Conduit (inches) AC Input to UPS 1-1/4 (A, B, C, Gnd) 208/220...
Page 190
Table U. Power Cable Conduit Requirements Powerware 9330 (35 kVA -- 40 kVA) Minimum Number of Powerware Conduit Number of Voltage Terminal Wires in Trade Size System Conduits Conduit (inches) AC Input to UPS 1-1/4 (A, B, C, Gnd) 208/220...
Page 191
When the optional Options Cabinet is used, source protection for the AC input should be treated as if you were supplying a 20 kVA three phase transformer for the Powerware 9330 (10 kVA---20 kVA) and a 40 kVA three phase transformer for the Powerware 9330 (25 kVA---40 kVA), to allow for inrush current.
Page 192
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at the computed voltage. DESCRIPTION: POWER WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201300---1 17 of 17 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---18 164201300 Rev. N 013004...
Page 193
Contacts used to indicate Battery Low status of UPS DESCRIPTION: CUSTOMER INTERFACE WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201300---2 1 of 5 REVISION: G DATE: 051502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---19 164201300 Rev. N 013004...
Page 194
Monitor Panel. Use twisted pair wires for each alarm input and common. CUSTOMER INTERFACE WIRING DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201300---2 2 of 5 REVISION: G DATE: 061502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---20 164201300 Rev. N 013004...
Page 195
REFER TO DRAWING 164201300--- 8 SERIAL PORT FOR LOCATION OF CSB DESCRIPTION: CUSTOMER INTERFACE WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201300---2 3 of 5 REVISION: G DATE: 061502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---21 164201300 Rev. N 013004...
Page 196
UPS is in normal operating mode. DESCRIPTION: CUSTOMER INTERFACE WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201300---2 4 of 5 REVISION: G DATE: 051502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---22 164201300 Rev. N 013004...
Page 197
NOTE: This switch must be a dedicated switch not tied into any other circuits. DESCRIPTION: CUSTOMER INTERFACE WIRING INSTALLATION NOTES DRAWING NO: SHEET: 164201300---2 5 of 5 REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---23 164201300 Rev. N 013004...
Page 198
From Sides of Cabinet Allow space for Options and Battery Cabinets DESCRIPTION: PHYSICAL FEATURES AND REQUIREMENTS DRAWING NO: SHEET: 164201300---3 1 of 2 REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---24 164201300 Rev. N 013004...
Page 199
8.3 (2.1) 480/208, 600/208 10.7 (2.7) 40 KVA 480/480 14.3 (3.6) DESCRIPTION: PHYSICAL FEATURES AND REQUIREMENTS DRAWING NO: SHEET: 164201300---3 2 of 2 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---25 164201300 Rev. N 013004...
Page 200
CABINET (OPTIONAL) CABINET OPTIONS CABINET POWERWARE 9330 (10 kVA---20 kVA) DESCRIPTION: TYPICAL UPS SYSTEM DRAWING NO: SHEET: 164201300---4 1 of 2 REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---26 164201300 Rev. N 013004...
Page 201
(OPTIONAL) CABINET OPTIONS CABINET (OPTIONAL) POWERWARE 9330 (25 kVA---40 kVA) DESCRIPTION: TYPICAL UPS SYSTEM DRAWING NO: SHEET: 164201300---4 2 of 2 REVISION: G DATE: 061502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---27 164201300 Rev. N 013004...
Page 202
DESCRIPTION: UPS SYSTEM CONFIGURATIONS supplied. DRAWING NO: SHEET: 164201300---5 1 of 3 NOTE 2: Output Voltage must match Bypass Input Voltage. REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---28 164201300 Rev. N 013004...
Page 203
DESCRIPTION: UPS SYSTEM CONFIGURATIONS supplied. DRAWING NO: SHEET: 164201300---5 2 of 3 NOTE 2: Output Voltage must match Bypass Input Voltage. REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---29 164201300 Rev. N 013004...
Page 204
DESCRIPTION: UPS SYSTEM CONFIGURATIONS supplied. DRAWING NO: SHEET: 164201300---5 3 of 3 NOTE 2: Output Voltage must match Bypass Input Voltage. REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---30 164201300 Rev. N 013004...
Page 205
POWERWARE 9330 (25 kVA---40 kVA) DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM NOTE 1: Remove jumper for dual feed. DRAWING NO: SHEET: 164201300---6 1 of 1 REVISION: DATE: 041503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---31 164201300 Rev. N 013004...
Page 206
164201300---7 1 of 18 CONFIGURATION CONFIGURATION SINGLE FEED; INPUT TRANSFORMER; SINGLE FEED; INPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITHOUT DISTRIBUTION BYPASS SWITCH; WITH DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---32 164201300 Rev. N 013004...
Page 207
164201300---7 2 of 18 CONFIGURATION CONFIGURATION SINGLE FEED; INPUT TRANSFORMER; SINGLE FEED; INPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITHOUT DISTRIBUTION BYPASS SWITCH; WITH DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---33 164201300 Rev. N 013004...
Page 208
WITH DISTRIBUTION DRAWING NO: SHEET: CONFIGURATION CONFIGURATION 164201300---7 3 of 18 SINGLE FEED; BYPASS SWITCH; SINGLE FEED; BYPASS SWITCH; REVISION: DATE: 013004 WITH DISTRIBUTION WITHOUT DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---34 164201300 Rev. N 013004...
Page 209
DRAWING NO: SHEET: 164201300---7 4 of 18 SINGLE FEED; OUTPUT TRANSFORMER; SINGLE FEED; OUTPUT TRANSFORMER; REVISION: DATE: BYPASS SWITCH; WITH DISTRIBUTION BYPASS SWITCH; WITHOUT DISTRIBUTION 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---35 164201300 Rev. N 013004...
Page 210
OPTIONS CABINET SCHEMATICS BYPASS SWITCH; WITHOUT DISTRIBUTION DRAWING NO: SHEET: 164201300---7 CONFIGURATION 5 of 18 SINGLE FEED; OUTPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITHOUT DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---36 164201300 Rev. N 013004...
Page 211
SINGLE FEED; BYPASS INPUT TRANSFORMER SINGLE FEED; BYPASS INPUT TRANSFORMER AND OUTPUT TRANSFORMER; OUTPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITH DISTRIBUTION BYPASS SWITCH; WITH DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---37 164201300 Rev. N 013004...
Page 212
TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION DRAWING NO: SHEET: 164201300---7 7 of 18 CONFIGURATION SINGLE FEED; BYPASS INPUT TRANSFORMER AND OUTPUT REVISION: DATE: 013004 TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---38 164201300 Rev. N 013004...
Page 213
TRANSFORMER; BYPASS SWITCH; WITH DISTRIBUTION DRAWING NO: SHEET: 164201300---7 8 of 18 CONFIGURATION DUAL FEED; MAINS INPUT TRANSFORMER; OUTPUT REVISION: DATE: 013004 TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---39 164201300 Rev. N 013004...
Page 214
OPTIONS CABINET SCHEMATICS CONFIGURATION DRAWING NO: SHEET: 164201300---7 DUAL FEED; MAINS INPUT TRANSFORMER; OUTPUT 9 of 18 TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---40 164201300 Rev. N 013004...
Page 215
164201300---7 10 of 18 CONFIGURATION CONFIGURATION SINGLE FEED; INPUT TRANSFORMER; SINGLE FEED; INPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITHOUT DISTRIBUTION BYPASS SWITCH; WITH DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---41 164201300 Rev. N 013004...
Page 216
164201300---7 11 of 18 CONFIGURATION CONFIGURATION SINGLE FEED; INPUT TRANSFORMER; SINGLE FEED; INPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITHOUT DISTRIBUTION BYPASS SWITCH; WITH DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---42 164201300 Rev. N 013004...
Page 217
WITH DISTRIBUTION DRAWING NO: SHEET: 164201300---7 12 of 18 CONFIGURATION CONFIGURATION SINGLE FEED; BYPASS SWITCH; SINGLE FEED; BYPASS SWITCH; REVISION: DATE: 013004 WITHOUT DISTRIBUTION WITH DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---43 164201300 Rev. N 013004...
Page 218
164201300---7 13 of 18 CONFIGURATION CONFIGURATION SINGLE FEED; OUTPUT TRANSFORMER; SINGLE FEED; OUTPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITH DISTRIBUTION BYPASS SWITCH; WITHOUT DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---44 164201300 Rev. N 013004...
Page 219
OPTIONS CABINET SCHEMATICS BYPASS SWITCH; WITHOUT DISTRIBUTION DRAWING NO: SHEET: 164201300---7 CONFIGURATION 14 of 18 SINGLE FEED; OUTPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITHOUT DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---45 164201300 Rev. N 013004...
Page 220
SINGLE FEED; BYPASS INPUT TRANSFORMER SINGLE FEED; BYPASS INPUT TRANSFORMER AND OUTPUT TRANSFORMER; OUTPUT TRANSFORMER; REVISION: DATE: 013004 BYPASS SWITCH; WITH DISTRIBUTION BYPASS SWITCH; WITH DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---46 164201300 Rev. N 013004...
Page 221
TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION CONFIGURATION DRAWING NO: SHEET: 164201300---7 16 of 18 SINGLE FEED; BYPASS INPUT TRANSFORMER AND OUTPUT REVISION: DATE: TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---47 164201300 Rev. N 013004...
Page 222
TRANSFORMER; BYPASS SWITCH; WITH DISTRIBUTION DRAWING NO: SHEET: 164201300---7 17 of 18 CONFIGURATION DUAL FEED; MAINS INPUT TRANSFORMER; OUTPUT REVISION: DATE: 013004 TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---48 164201300 Rev. N 013004...
Page 223
OPTIONS CABINET SCHEMATICS CONFIGURATION DRAWING NO: SHEET: 164201300---7 18 of 18 DUAL FEED; MAINS INPUT TRANSFORMER; OUTPUT TRANSFORMER; BYPASS SWITCH; WITHOUT DISTRIBUTION REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---49 164201300 Rev. N 013004...
COMPARTMENT MUST BE REMOVED POWERWARE 9330 (10 kVA-- 20 kVA) TO GAIN ACCESS TO WIRING TERMINALS. DRAWING NO: SHEET: 164201300---8 1 of 5 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---50 164201300 Rev. N 013004...
Page 225
POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---8 2 of 5 NOTE: REMOVE JUMPERS BETWEEN CB1 AND TERMINAL BLOCK FOR DUAL INPUT. REVISION: DATE: 021503 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---51 164201300 Rev. N 013004...
Page 226
NEUTRAL LEFT VIEW DESCRIPTION: LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---8 3 of 5 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---52 164201300 Rev. N 013004...
Page 227
OR PUNCH CONDUIT HOLES.) DESCRIPTION: LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---8 4 of 5 REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---53 164201300 Rev. N 013004...
Page 228
POWER CONNECTOR LOCATION OF UPS CABINET TERMINALS DESCRIPTION: POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---8 5 of 5 REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---54 164201300 Rev. N 013004...
Page 229
COMPARTMENT, AND CB1 MUST BE POWERWARE 9330 (25 kVA-- 40 kVA) REMOVED TO GAIN ACCESS TO WIRING TERMINALS. DRAWING NO: SHEET: 164201300---9 1 of 8 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---55 164201300 Rev. N 013004...
Page 230
LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) FRONT VIEW DETAIL DRAWING NO: SHEET: 164201300---9 2 of 8 SINGLE INPUT REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---56 164201300 Rev. N 013004...
Page 231
POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---9 3 of 8 NOTE: REMOVE JUMPERS BETWEEN REVISION: DATE: 101502 TERMINAL BLOCKS FOR DUAL INPUT. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---57 164201300 Rev. N 013004...
Page 232
WIREWAY LEFT VIEW DESCRIPTION: LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---9 4 of 8 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---58 164201300 Rev. N 013004...
Page 233
LEFT VIEW DETAIL DESCRIPTION: LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---9 5 of 8 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---59 164201300 Rev. N 013004...
Page 234
OR PUNCH CONDUIT HOLES.) DESCRIPTION: LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---9 6 of 8 REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---60 164201300 Rev. N 013004...
Page 235
OR PUNCH CONDUIT HOLES.) DESCRIPTION: LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---9 7 of 8 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---61 164201300 Rev. N 013004...
Page 236
POWER CONNECTOR DESCRIPTION: LOCATION OF UPS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---9 8 of 8 REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---62 164201300 Rev. N 013004...
Page 237
SWITCH (MBS) GROUND TERMINALS DESCRIPTION: LOCATION OF OPTIONS CABINET TERMINALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---10 1 of 6 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---63 164201300 Rev. N 013004...
Page 238
WITH ARTICLE 356 OF THE NEC.) DESCRIPTION: LOCATION OF OPTIONS CABINET TERMINALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---10 2 of 6 REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---64 164201300 Rev. N 013004...
Page 239
(SEE SHEET 3 FOR DETAILS) DESCRIPTION: LOCATION OF OPTIONS CABINET TERMINALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---10 3 of 6 REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---65 164201300 Rev. N 013004...
Page 240
TERMINAL STRIP TB1 DESCRIPTION: LOCATION OF OPTIONS CABINET TERMINALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---10 4 of 6 REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---66 164201300 Rev. N 013004...
Page 241
OR PUNCH CONDUIT HOLES.) DESCRIPTION: LOCATION OF OPTIONS CABINET TERMNALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---10 5 of 6 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---67 164201300 Rev. N 013004...
Page 242
COVER PANEL REMOVED DESCRIPTION: LOCATION OF OPTIONS CABINET TERMNALS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---10 6 of 6 REVISION: DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---68 164201300 Rev. N 013004...
Page 243
MAINTENANCE BYPASS SWITCH (MBS) DESCRIPTION: LOCATION OF OPTIONS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---11 1 of 4 REVISION: DATE: 081502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---69 164201300 Rev. N 013004...
Page 244
(SEE SHEET 3 FOR DETAILS) GROUND TERMINALS DESCRIPTION: LOCATION OF OPTIONS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---11 2 of 4 REVISION: DATE: 081502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---70 164201300 Rev. N 013004...
Page 245
TERMINAL STRIP TB1 DESCRIPTION: LOCATION OF OPTIONS CABINET TERMNALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---11 3 of 4 REVISION: DATE: 081502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---71 164201300 Rev. N 013004...
Page 246
PUNCH CONDUIT HOLES.) HOLES.) DESCRIPTION: LOCATION OF OPTIONS CABINET TERMINALS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---11 4 of 4 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---72 164201300 Rev. N 013004...
Page 247
LOCATION OF BATTERY CABINET TERMINALS POWERWARE 9330 (10 kVA-- 20 kVA) POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---12 1 of 1 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---73 164201300 Rev. N 013004...
Page 248
UPS CABINET DIMENSIONS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---13 1 of 2 Dimensions are in millimeters and [inches] REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---74 164201300 Rev. N 013004...
Page 249
Dimensions are in millimeters and [inches] DESCRIPTION: UPS CABINET DIMENSIONS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---13 2 of 2 REVISION: DATE: 111501 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---75 164201300 Rev. N 013004...
Page 250
UPS CABINET DIMENSIONS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---14 1 of 4 Dimensions are in millimeters and [inches] REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---76 164201300 Rev. N 013004...
Page 251
UPS CABINET DIMENSIONS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---14 2 of 4 Dimensions are in millimeters and [inches] REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---77 164201300 Rev. N 013004...
Page 252
Dimensions are in millimeters and [inches] DESCRIPTION: UPS CABINET DIMENSIONS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---14 3 of 4 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---78 164201300 Rev. N 013004...
Page 253
Dimensions are in millimeters and [inches] DESCRIPTION: UPS CABINET DIMENSIONS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---14 4 of 4 REVISION: DATE: 071501 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---79 164201300 Rev. N 013004...
Page 254
OPTIONS CABINET DIMENSIONS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---15 Dimensions are in millimeters and [inches] 1 of 4 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---80 164201300 Rev. N 013004...
Page 255
Dimensions are in millimeters and [inches] DESCRIPTION: OPTIONS CABINET DIMENSIONS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---15 2 of 4 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---81 164201300 Rev. N 013004...
Page 256
OPTIONS CABINET DIMENSIONS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: Dimensions are in millimeters and [inches] 164201300---15 3 of 4 REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---82 164201300 Rev. N 013004...
Page 257
Dimensions are in millimeters and [inches] DESCRIPTION: OPTIONS CABINET DIMENSIONS POWERWARE 9330 (10 kVA-- 20 kVA) DRAWING NO: SHEET: 164201300---15 4 of 4 REVISION: N DATE: 013004 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---83 164201300 Rev. N 013004...
Page 258
OPTIONS CABINET DIMENSIONS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---16 Dimensions are in millimeters and [inches] 1 of 2 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---84 164201300 Rev. N 013004...
Page 259
Dimensions are in millimeters and [inches] DESCRIPTION: OPTIONS CABINET DIMENSIONS POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---16 2 of 2 REVISION: DATE: 053001 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---85 164201300 Rev. N 013004...
BATTERY CABINET DIMENSIONS POWERWARE 9330 (10 kVA-- 20 kVA) POWERWARE 9330 (25 kVA-- 40 kVA) DRAWING NO: SHEET: 164201300---17 1 of 1 REVISION: DATE: 101502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---86 164201300 Rev. N 013004...
Page 261
1/2” CONDUIT (5 PLACES) DESCRIPTION: TYPICAL REMOTE EMERGENCY POWER OFF DRAWING NO: SHEET: 164201300---18 1 of 2 Dimensions are in millimeters and [inches] REVISION: DATE: 051502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---87 164201300 Rev. N 013004...
Page 262
Remote Emergency Power Off DIMENSIONS switch and the UPS are to be DRAWING NO: SHEET: 164201300---18 supplied by the customer. 2 of 2 REVISION: DATE: 051502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---88 164201300 Rev. N 013004...
Remote Monitor Panel and the DRAWING NO: SHEET: UPS mounted Remote Monitor Card 164201300---19 1 of 1 are to be supplied by the customer. REVISION: G DATE: 051502 Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---89 164201300 Rev. N 013004...
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation A ---90 164201300 Rev. N 013004...
Page 265
All parts requiring replacement for the Factory Warranty period. If, in the opinion of Powerware, the Unit fails to meet published specifications and the defect is within the terms of this warranty, the Unit will be repaired or replaced at the option of Powerware with no charge for replacement parts. Labor required, to make...
Page 266
This Page Intentionally Left Blank. Powerware 9330 (10 kVA- -40 kVA) Installation and Operation W--2 164201300 Rev. N 013004...