Page 1
® powerware Prestige Series 6000 VA Installation and Operator’s Manual for IBM Applications...
Page 2
Novell is a registered trademark of Novell, Inc. 3Com is a registered trademark of 3Com Corporation. Copyright 1995-2000 Powerware Corporation, Raleigh, North Carolina, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware Corporation.
Page 3
UICK NSTALL UPS with PPDM Installation C A U T I O N Read the safety instructions beginning on page 7 before installing the UPS. If you are connecting the UPS to an AS/400, the QUPSDLYTIM system value for the UPS Monitoring feature should be set.
Page 5
Quick Install For the AS/400 interface, plug the AS/400 communications cable into the serial port on the UPS rear panel. Plug the other end of the cable into the J14 connector on your AS/400.
Page 6
Quick Install This page intentionally left blank.
VA requirement. NOTE For the load ratings of AS/400 models and attachable devices, see Chapter 9 of “AS/400 Physical Planning Reference,” SC41-5109. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 11
Computers, monitors, and modems typically have a higher priority because they could be processing or transmitting data when a power outage occurs. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
2. In Figure 3, enter the number of battery cabinets that you have installed. Find the intersection point of the appropriate Load (VA) and number of battery cabinets in the “Prestige 6000 with PPDM” table on page 5. Enter this number in Figure 3, Total Battery Time Minutes.
Page 13
Introduction Prestige 6000 with PPDM Approximate Battery Time (in Minutes) Load (VA) Load (VA) Load (W) Load (W) at 0.67 PF* 2 Cabinets 3 Cabinets 4 Cabinets 5 Cabinets 6 Cabinets 1500 1000 3000 2000 4500 3000 6000 4000 Typical Power Factor (PF) NOTE For AS/400 usage, see “Base Equipment”...
Keep covered when not in use. - Indicates the input to a unit. INPUT OUTPUT - Indicates the output from a unit. - Indicates the Maintenance Bypass switch. BYPASS Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Please note that the output sockets on the UPS are electrically live whenever the UPS Output On button is pressed, even if the input cord is disconnected. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 16
Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 17
Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 18
Voor Bypass Module systemen met vast-bedrade uitgangen, moeten de juiste hoofdschakelaars voor wisselstroom uitgangcircuit(s) door derden worden geleverd. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 19
UPSin lähtöteho PÄÄLLÄ -painiketta ( ), riippumatta siitä, onko tulokaapeli kytkettynä tai ei. Palovaaran vähentämiseksi UPS ja ohituslaite tulee kytkeä virtapiiriin, jonka haaroitusjohtojen ylivirtasuojauksen maksimiarvo on 30 A. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 20
Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous peine de supprimer la mise à la terre de l’onduleur et du matériel connecté. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 21
Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 22
Für Bypass-Systeme mit festverdrahteten Eingängen muß der Überstromschutz für die Ausgangswechselstromkreise anderweitig bereitgestellt werden. Für Bypass-Systeme mit festverdrahteten Ausgängen müssen Trennschalter für die Ausgangswechselstromkreise mit passendem Nennwert anderweitig bereitgestellt werden. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Osservare le apposite istruzioni. le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 25
Bypass provvisti di uscite cablate, i sezionatori di corrente nominale adeguata per il/i circuito/i a corrente alternata in uscita devono essere forniti da terzi. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
For PPDM systemer med fastkoplete uttak, må overstrømvern for vekselstrømuttak(ene) stilles til rådighet av andre. For PPDM systemer med fastkoplete uttak, må passende utkoplingsbrytere for vekselstrømuttak(ene) stilles til rådighet av andre. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 27
Favor observar que o soquete de alimentação de saída na UPS estará eletricamente ativo todas as vezes que o interruptor ( ) estiver pressionado, indiferente à presença de energia elétrica na rede de alimentação. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 28
Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут взорваться под воздействием огня. Никогда не открывайте и не деформируйте аккумуляторы. Вытекающий электролит опасен для кожи и глаз, и может быть крайне токсичным. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 29
по току выходной(ых) цепи(ей) переменного тока должна обеспечиваться сторонними организациями. Для блока байпаса с неразъемными выходами сторонними организациями должны быть обеспечены выключатели выходной(ых) цепи(ей) переменного тока, рассчитанные на соответствующий номинал. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
El interruptor de encendido/apagado del SIE no tiene aislación eléctrica de las partes internas. Desenchufe el cable de entrada del tomacorriente de la pared cuando desconecte la unidad durante períodos largos. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 31
Använda batterier får aldrig brännas upp. De kan explodera. Öppna aldrig batterierna eller ta isär dem. Utsläppt elektrolyt är skadlig för hud och ögon och kan vara mycket giftig. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 32
Överströmsskydd för de utgående växelströmkretsarna ska tillhandahållas av andra för fast anslutna förbikopplingssystem. Strömbrytare för bortkoppling med passande dimensioner för de utgående växelströmkretsarna ska tillhandahållas av andra för fast anslutna förbikopplingssystem. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 33
Safety Warnings Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 34
Safety Warnings Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 35
Safety Warnings Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 36
Safety Warnings Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 37
Safety Warnings Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 38
Safety Warnings This page intentionally left blank. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Whenever the units are not energized, verify the circuit breaker on all battery cabinets is returned to the OFF (O) position (see Figure 9 on page 36). Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Do not place more than six cabinets in one stack (the PPU is equal to two cabinets and the PPDM is equal to two cabinets). Vents Battery Cabinets PPDM Figure 4. UPS with PPDM Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 41
For ungrounded output neutral applications only. Remove the ground screw, rotate the ground cover until it snaps into place, and reinstall the ground screw in the ungrounded position (see Figure 6). Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 42
Utility Input To IEC 320-C19 PowerPass (Cord Receptacle Attached) IEC 309 Receptacle Bypass Switch Circuit Protectors IEC 320-C13 Receptacles Figure 7. IEC 309 PPDM Rear Panel Connections Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 43
Figure 8. L6-30R/5-15R PPDM Rear Panel Connections 4. Verify the circuit breaker on all battery cabinets is in the OFF (O) position (see Figure 9). Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 44
Battery Connector Guard Battery Connector Output REPO Voltage Battery Breaker Tie Receptacle Receptacle Selector Circuit Battery Cabinets Switch Breaker Figure 9. UPS with Battery Cabinets (Rear View) Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 45
Output Voltage” on page 49). Changing the output voltage while the UPS is operating may cause an emergency power-off. Voltage Selector Switch Figure 10. Voltage Selector Switch Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 46
10. Remove the breaker tie from the circuit breaker on all battery cabinets. 11. If you are using a REPO switch, follow the “REPO Installation” instructions on page 41. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
AC receptacle that has been wired in accordance with NEC specifications or national wiring rules. See Chapter 6, “Specifications” on page 65 for the input current/output voltage requirements. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 48
To restart the UPS, follow the startup procedure beginning on page 39. NOTE If the REPO test fails and the UPS does not shutdown, contact your service representative. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
3. Pivot the REPO receptacle guard out of the way, plug the REPO plug/receptacle PPU connector into the REPO receptacle on the PPU rear panel and twist the connector in place (see Figure 9 on page 36). Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 50
Tighten the compression terminals with a screwdriver (see Figure 12). Mounting Holes Plug/Receptacle PPU Connector Access Hole for Conduit Three Foot Cord Terminal Block Figure 12. Optional REPO Cord Junction Box Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
If the Battery Fault indicator flashes, operate the UPS for 24 hours to fully charge the battery. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 52
Installation This page intentionally left blank. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Unlit Amber Overload Indicator Green Site Fault Indicator Flashing Overtemp Indicator Battery Fault Indicator Self Test Indicator Battery Online Indicator Figure 13. UPS Front Panel Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
LOAD ON LOAD ON LOAD OFF APPROX. APPROX. APPROX. APPROX. NORMAL 81-100% 61-80% 41-60% 0-40% UTILITY LOAD LOAD LOAD LOAD Figure 15. Normal Operation Indicators Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
If battery capacity becomes low while in Battery mode, the Battery Fault indicator begins to flash and the Self Test indicator remains lit, indicating approximately two minutes before UPS shutdown. The alarm beeps every two seconds. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
This feature allows you to start the UPS without utility power. After utility power has been unavailable for one minute, press and hold the Output On button until the alarm beeps. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
2. Select the new voltage (see Step 5 on page 37). 3. Restart the UPS by performing a UPS startup as described on page 39. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Do not set QUPSDLYTIM to “*NOMAX” unless you understand the implications of the “*NOMAX” function as described in one of the IBM documents listed above. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
3. Switch the PPU input breaker to the OFF (O) position. The UPS enters Battery mode for several seconds. The indicator turns off and the UPS shuts down. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 60
Output Battery Voltage Selector Input Receptacles Receptacle Connector Switch Breaker REPO Receptacle PPDM Figure 19. UPS with PPDM Rear Panel Connections (L6-30R/5-15R PPDM Model Shown) Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Do not turn the Voltage Selector switch while the UPS is operating (see “Changing the Output Voltage” on page 49). Changing the output voltage while the UPS is operating may cause an emergency power-off. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 62
The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
For assistance with IBM 9910 UPSs, see Chapter 8, “Service and Support” on page 75. If you want to change the UPS configuration settings, use the front panel or the UPS Serial Communications Menu. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Select this mode for the OnliSafe software. OVERLOAD OVERLOAD SITE FAULT SITE FAULT OVERTEMP OVERTEMP BATTERY BATTERY SELF TEST SELF TEST Figure 21. Front Panel Communication Options Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 65
6. Press the Output On button again to return the UPS to Normal mode. NOTE Printer mode selections are the only serial communication modes available from the front panel. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
The new settings are not effective until you select save from the Main Menu. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 67
P > Printer Dump attached printer. allows you to configure the UPS for a new L > LAN Configuration LAN mode and displays the Select LAN Configuration Menu. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 68
VUDGfA6DG v hpvr r GPXf76UU v hpvr pyrq " VUDGfA6DG v hpvr pyrq GPXf76UU v hpvr r VUDGfA6DG v hpvr r GPXf76UU v hpvr r UP RVDU UCDT H@IV @IU@S T@G@8UDPI 323 Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Chapter 8, “Service and Support” on page 75 for the number to call in your location. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
50 ft (15m). See Figure 22 for the location of the serial port. PPU Rear Panel Serial Port Serial Port Detail Figure 22. Serial Port Location Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Closed Low Battery Low Battery 23/24 Closed Signal Ground 12/15/18/25 NOTE Pin numbers separated by a forward slash ( / ) are connected together internally. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 72
Communication This page intentionally left blank. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
C H A P T E R 6 PECIFICATIONS Prestige 6000 Specifications The following model specifications assume: 88% efficiency at full load (Normal mode) Input power factor of 0.95 84% efficiency running on battery Model 6000 UPS (Nominal Operating Specifications)
C to 40 F to 104 Humidity: 5 to 95% (noncondensing) Agency Approvals Safety: EN50091-1 UL 1778 EMC: FCC Part 15 Class A EN50091-2 Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Use the following tables to determine load wiring requirements when the PPDM is used with the UPS. The distribution of your load on the available outputs of the PPDM may affect the maximum load obtainable. Prestige 6000 PPDM Ratings with a Model 6000 UPS PPDM Model Input Utility Voltage...
All models include power processing unit, PowerPass Distribution Module (208V or 240V) input line cord, AS/400 communications cable, operator’s manual, and two battery packs. Standard Accessories IBM Part Number IBM Type/Model Description 9910-6603 Prestige 6000 Full Battery Pack (Qty. 2) 17G1796 9910-6558 Prestige 6000 PowerPass Distribution Module (120/240 IEC 309) 17G1795 9910-6557...
Manuals IBM Order Number Description SC21-8380 Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Manuals may be ordered from the IBM Mechanicsburg Distribution Center. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 78
Specifications This page intentionally left blank. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Verify cable integrity (see page 62). function properly. Incorrect baud rate. Select a new baud rate (see page 61). Incorrect communication mode. Select a new communication mode (see Chapter 5). Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 80
Verify that the battery cabinet breaker is in the ON ( ) position. Battery cabinet is not properly Verify that the battery cords are connected to the UPS. connected. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Output On button for one second. The alarm becomes quiet. If UPS status changes, the alarm beeps, overriding previous alarm silencing. Press the Output On button again to silence the alarm. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 82
Troubleshooting This page intentionally left blank. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
7. Publications may be ordered from the IBM Mechanicsburg Distribution Center. Connected Equipment Insurance With this program, Powerware Corporation provides a $25,000 Powerware Protection Guarantee. See page 85 for specific terms and conditions of the Powerware Protection Guarantee. Powerware ®...
Page 84
Service and Support Battery Warranty If, in Powerware Corporation’s opinion, the unit fails to meet published specifications and the defect is within the terms of the limited warranty (attached), the defective part(s) will be repaired or replaced at the option of Seller with no charge for replacement parts. The battery is...
Page 85
Return Material Authorization (RMA). The packaging material used for the replacement unit can be used for this purpose. Shipping Powerware will pay all shipping costs incurred (both to and from the customer site or IBM Designated Location) to replace the defective UPS system. Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 86
Customer Process for Service 1. Customer calls the local IBM office servicing account. 2. The IBM CE responds, determines the problem, and resolves the problem. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Under NO CONDITIONS are IBM Customer Engineers authorized to remove the covers from any of the UPS modules. The UPSs for this program are warranted by Powerware Corporation for up to five (5) years. Warranty time may vary from country to country as per local regulations.
Page 88
A recommended distance between the UPS is one floor tile. Raised Floor Tiles Additional < Frames S/390 9910 Front Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 89
The warranty period is five years from the date of installation or 66 months from the date of manufacture, whichever occurs first. If, in Powerware Corporation’s opinion, the unit fails to meet published specifications and the defect is within the terms of the limited warranty (attached), the defective part(s) will be repaired or replaced at the option of Seller with no charge for replacement parts.
Page 90
Configurations There are many configurations of UPS and S/390 models and options. The following are basic examples of the Powerware Corporation UPSs and IBM S/390 processors. The type and part number of the line cord, sense and power cable will vary depending upon customer power connection, S/390 model, and features.
Page 91
IBM Service Should IBM Service require technical assistance, contact Powerware Corporation at 919-870-3028. Part Numbers The following are the IBM part numbers assigned to the Powerware Corporation modules: 46H9377 - Power Processing Unit 46H9378 - PowerPass Distribution Module 46H9379 - Battery Cabinet...
Page 92
(66) months from the date of completion of manufacture, whichever period expires first. If, in Powerware Corporation’s opinion, the unit fails to meet published specifications and the defect is within the terms of this limited warranty, the defective part(s) will be repaired or replaced at the option of Seller with no charge for replacement parts.
Page 93
Program Summary: Powerware Corporation guarantees to repair or replace (at the option of Powerware Corporation) any equipment that is damaged by AC power disturbances when said equipment is properly connected to a Powerware Corporation uninterruptible power supply (UPS) covered by the Powerware Protection Guarantee. This program provides for reimbursement of repair or replacement expenses up to $25,000.00 and applies only to component or physical system...
Page 94
Service and Support This page intentionally left blank. Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Control-C, 58 input connector, 36 Control-E, 59 installation, 32 cord, power, 39, 66 output connector, 36 rear panel, 36 Custom LAN Configuration storage, 31 Menu, 60 Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 96
Inverter Shutdown Control, 60 Normal Mode, 46 indicator, 45 LAN Configuration Novell Network Interface Main Menu option, 58 front panel configuration, 56 menu, 60 LAN Configuration Menu, 60 Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 97
37, 53 ratings, 62 installation, 32 serial cable, 62 Maintenance Bypass feature, 32 operation, 51 serial port, description, 62 Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 98
Terminal Modes, 59 Tests Battery (on demand), 48 warranty diagnostic, 48 battery AS/400 9910, 76 troubleshooting chart, 71 S/390 9910, 81 tips, 43 IBM five-year, 84 Powerware ® Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy...
Page 99
Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...
Page 100
164200291 E Powerware Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA) Uncontrolled Copy ®...