Default Settings

Aux Menu

Connections Menu

B–6
Item
Manual Aux
Active Lvl
a
Trigger Src
Trigger Level—LowBattV
Trigger Level—HighBattV
Trigger Level—HighBattTemp 45.0°C
Trigger Level—LowBattTemp
Trigger Delay
Clear Level—LowBattV
Clear Level—HighBattV
Clear Level—HighBattTemp
Clear Level—LowBattTemp
Clear Delay
a.The Trigger Src setting (and the settings below Trigger Src) appear only if Man-
ual Aux setting has been set to Automatic.
b.Trigger Level, Trigger Delay, Clear Level and Clear Delay do not appear if Trig-
ger Src is set to Fault.
Item
Default
DCConn
HouseBatt1
ACOut
ACLoad1
AC1
Grid 1
AC2
Gen 1
Default
24 V
48 V
ManualOff
ActiveHigh
LowBattV
b
22.0V
44.0V
28.0V
56.0V
0.0°C
1s
24.0V
48.0V
26.0V
52.0V
35.0°C
5.0°C
1s
Range
HouseBatt1–6, StartBatt1–6
ACLoad1–10
None, Grid1–10, Gen1–10,
None, Grid1–10, Gen1–10,
Range
24 V
48 V
ManualOn, ManualOff,
Automatic
ActiveHigh, ActiveLow
LowBattV, HighBattV,
LowBattTemp,
HighBattTemp, Fault
10.0–26.0V 20.0–52.0V 0.1
24.0–32.0V 48.0–64.0V 0.1
30.0–60.0°C
-30.0–10.0°C
0–600s
10.0–26.0V 20.0–52.0V 0.1
24.0–32.0V 48.0–64.0V 0.1
30.0–60.0°C
-30.0–10.0°C
0–600s
975-0240-01-01
Step
Size
n/a
n/a
n/a
1
1
1
1
1
1