Default Settings

Custom Battery Menu

AC Menu

B–4
Default Setting
Item
24 V
Eqlz Support
Enabled
Eqlz Voltage
32.0V
Bulk Voltage
28.8V
28.4V (Gel)
28.6V (AGM)
Absorb
28.8V
Voltage
28.4V (Gel)
28.6V (AGM)
Float Voltage
27V
27.6V (Gel)
26.8V (AGM)
Absorb Time
180min
Batt Temp
27mV/C
Comp
(Flooded, Gel)
21mV/C (AGM)
a.Custom battery default settings are based on the Flooded battery default settings.
The Gel and AGM default settings are provided here for reference only.
Default Setting
Item
120 Vac
AC Priority
AC1
AC1 Breaker
60A
AC1 Lo Volt
106V
AC1 Hi Volt
132V
AC1 Lo Freq
55Hz
AC1 Hi Freq
65Hz
AC2 Breaker
60A
AC2 Lo Volt
80V
AC2 Hi Volt
138V
AC2 Lo Freq
55Hz
AC2 Hi Freq
65Hz
a
48 V
Enabled
64.0V
57.6V
56.8V (Gel)
57.2V (AGM)
57.6V
56.8V (Gel)
57.2V (AGM)
54.0V
55.2V (Gel)
53.6V (AGM)
180min
108mV/C
(Flooded, Gel)
42mV/C (AGM)
Range
240 Vac
120 Vac
AC1, AC2
5–60A
212V
78–115V
264V
125–140V
52–59Hz
61–68Hz
5–60A
160V
78–115V
276V
125–140V
52–59Hz
61–68Hz
Range
24 V
48 V
Enabled, Disabled
27.0–32.0V 54.0–64.0V 0.1V
20.0–32.0V 40.0–64.0V 0.1V
20.0–32.0V 40.0–64.0V 0.1V
20.0–32.0V 40.0–64.0V 0.1V
1–480min
0–180mV/C
240 Vac
Step Size
n/a
1A
156–230V
1V
250–280V
1V
1Hz
1Hz
1A
156–230V
1V
250–280V
1V
1Hz
1Hz
975-0240-01-01
Step
Size
n/a
1min
1mV/C