Troubleshooting
Table 4-5 Fault Messages
Fault
Number
Message
F57
FET1 Over
Temperature
Shutdown
F58
FET2 Over
Temperature
Shutdown
F59
GOCFG process
failed
F63
AC Overload
F64
AC Overload L1
4–24
Fault Type
Cause
Automatic
Internal temperature is
over 105 °C.
AC input voltage may be
too high while charging.
Operating too large of a
load for too long while
inverting.
Ambient temperature
may be high.
Inverter cooling fan may
have failed.
Inverter airflow intake
may be blocked.
Charging setting is too
high based on ambient
temperature around
inverter.
Automatic
See F57.
Manual
Auto-configuration
process failed.
Escalating
Excessive load on the
Auto Fault.
AC output.
Must occur 3
times in 5
minutes before
becoming a
manual fault.
Escalating
Excessive load on the
Auto Fault.
AC output.
Must occur 3
times in 5
minutes before
becoming a
manual fault.
Solution
Fault clears when temperature drops
to 75 °C.
Check for high input AC voltage.
Remove excessive loads.
Let inverter cool down and try
restarting.
Hold a piece of paper to inverter
vents to check the fan. If the fan has
failed, have the inverter serviced.
Increase clearance around the
inverter or unclog the fan air intake.
Lower the Max Charge Rate
setting.
See F57.
Retry the "Copy From?" procedure,
or configure the unit manually.
Check for loads above the inverter's
capacity. Turn off some loads if
necessary.
See F63
975-0240-01-01