Table 4-5 Fault Messages
Fault
Number
Message
F24
AI Under
Frequency
F25
AI Over Frequency
F26
AI Under
Frequency
F27
AI L1 Over Voltage
F28
AI L2 Over Voltage
F29
AI L1L2 Over
Voltage
F30
AI L1L2 Over
Voltage
F31
AI L1 Over Voltage
F32
AI L2 Over Voltage
F33
AI L1L2 Over
Voltage
F34
AI L1 Under
Voltage
F35
AI L2 Under
Voltage
F36
AI L1L2 Under
Voltage
F37
AI L1 Under
Voltage
975-0240-01-01
Fault Type
Cause
Automatic
Under-frequency anti-
islanding, caught by the
AC qualification limit.
Automatic
Over-frequency anti-
islanding, 60.4 Hz
Automatic
Under-frequency anti-
islanding, 59.4 Hz
Automatic
Over-voltage anti-
islanding, fast
disconnect, 135 Vac.
Automatic
See F27.
Automatic
Over-voltage anti-
islanding fault, caught by
the qualification limit,
voltage difference
between L1 and L2.
Automatic
Over-voltage anti-
islanding, fast
disconnect, 270 V.
Automatic
Over-voltage anti-
islanding, slow
disconnect, 130 V.
Automatic
Over-voltage anti-
islanding, slow
disconnect, 130 V.
Automatic
Over-voltage anti-
islanding, slow
disconnect, 260 V.
Automatic
Under-voltage anti-
islanding, slow
disconnect, 107 V.
Automatic
See F34.
Automatic
See F34.
Automatic
Under-voltage anti-
islanding, fast
disconnect, 66 Vac.
Faults and Warnings
Solution
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
4–21