Example Of Simple Set-Up - Mitsubishi Electric ME96NSR User Manual

Electronic multi-measuring instrument
Hide thumbs Also See for ME96NSR:
Table of Contents

Advertisement

Example of Simple Set-up

A simple set-up example is shown below.
■ Set-up example
■ Set-up procedures
Items that require set value change are shown in shade.
SET
RESET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Model type: ME96NSR (with ME-4201-NS96 optional plug-in module)
Phase wire: Three phase 4-wire Voltage display: Phase to phase
Measurement items: A, V, W, PF
Input voltage: 220V/380V direct
Primary current: 200A
Secondary current: 5A
Active power maximum scale: 160kW (standard: rating 100%)
Analog output: CH1(A
AVG
Pulse output: Imported active energy, Pulse unit: 10kW/pulse
Pressing simultaneously for 2 seconds
+
,
+
,
+
,
+
,
+
,
+
,
), CH2(V
), CH3( W, 160kW), CH4( PF, 0.5 to 1 to 0.5)