3.
How to Set up
Example for Easy Setup
The following example illustrates an easy setup.
■Setting Example
・
Model:
・
Phase wire system:
・
Measuring element:
・ Input Voltage:
・
CT primary current:
・ CT Secondary current: 5 A
・ MODBUS RTU:
■Setting Procedure
shows the item where setting change is necessary.
Operating mode
Press
Setting Menu
SET
Phase wire system
SET
Display pattern
SET
VT/Direct voltag
SET
Direct voltage
SET
CT secondary
current
SET
CTprimary
current
SET
Current demand
time period
SET
Setting Menu
SET
ME96SSEB-MB
3-phase 4-wire
A, V, W, PF
220/380 V
200 A
Address:
1,
Baud rates:
Note: For details on the settings, refer to 3.2.
and
simultaneously for 2 seconds
SET
RESET
Set the setting menu number to "1" and then press SET.
The factory default is set to "3P4 (3-phase 4-wire)." Just press SET.
The factory default is set to "P01." Just press SET.
The factory default is set to "no (Without VT)." Just press SET.
e
The factory default is set to "220/380 V." Just press SET.
The factory default is set to "5 A." Just press SET.
Set to "200 A" and then press SET.
The factory default is set to "0 s." Just press SET.
Set the setting menu number to "2" and then press SET.
19.2kbps,
Parity:
even,
Stop bit:
36
1