4. Set-up
4.9 Simplified Set-up
5 VT secondary
+
voltage
DISPLAY
SET
6 VT primary
+
voltage
DISPLAY
SET
7 CT primary
+
current
DISPLAY
SET
8 Time constant for
+
current demand
DISPLAY
SET
(Page change of
set-up display)
5 Set the secondary voltage values of VT in case of using VT.
If you set "0: direct input" on set up No.e, this content
cannot be set.
,
[3P3W]
1 : 100V
2 : 110V
3 : 220V
6 Set the primary voltage values of VT in case of using VT.
If you set "0: direct input" on set up No.e, this content
cannot be set
It is set by the top 3 digits voltage values and the exponent
values (10 to the n-th power).
The set-up order is the exponent values and the voltage
values.
,
Exponent values: 0 (10
Voltage values: the top 3 digits (0 to 9)
Example: Set-up to 10000V
Exponent values: 2
Voltage values: 100
7 Set the primary current values of CT.
It is set by the top 2 digits current values and the exponent
values (10 to the (n-1)th power).
The set-up order is the exponent values and the current
values.
,
Exponent values: 0 (10
Current values: the top 2 digits (0 to 9)
Example: Set-up to 50A
Exponent values: 1
Current values: 50
8 Set the time constant for calculating current demand.
00: 0s
01: 10s
02: 20s
,
03: 30s
04: 40s
05: 50s
06: 1min
07: 2min
08: 3min
09: 4min
[3P4W]
1 : 63.5V
2 : 100V
3 : 110V
4 : 115V
5 : 120V
0
= 1 time)
1
1 (10
= 10 times)
2
2 (10
= 100 times)
3
3 (10
= 1000 times)
-1
= 0.1 time)
0
1 (10
= 1 time)
1
2 (10
= 10 times)
2
3 (10
= 100 times)
3
4 (10
= 1000 times)
10: 5min
11: 6min
12: 7min
13: 8min
14: 9min
15: 10min
16: 15min
17: 20min
18: 25min
19: 30min