Advertisement

Installation 4. Wiring Diagram
Optional Plug-in Module : ME-4201-NS96
Optional Plug-in Module : ME-0052-NS96
1. Do not bunch the digital input/output signal cables with the main circuit or power cables,
or install them close to each other. Keep the distance between the digital input/output
signal cables and the main circuit or power cables, and high voltage lines are shown
below, when they run parallel to each other.
Note
2. Analog output signal cables should keep the distance from the other power cables and
input signal (VT, CT and auxiliary power) cables, and should not bunch them. And use
the shielded cables or twisted pair cables not to be affected the noise, serge and induction.
Also, the wiring cables are to be as short as possible.
3. In case of ME96NSR-MB with ME-4201-NS96, the ModBus interface and the analog
outputs do not have the insulation between them.
Conditions
Below 600V power lines
Other power lines
Length
30cm or more
60cm or more