4. Set-up
4.4 Bar Graph Set-up
In the operation mode, press the
operation becomes available.
Set-up menu
DISPLAY
SET
1 Current maximum
scale
DISPLAY
SET
2 Active power
maximum scale
DISPLAY
SET
3 Active power scale
DISPLAY
SET
4 Reactive power
maximum scale
DISPLAY
SET
5 Power factor scale
SET
Set-up menu
1. Accuray is defined to rated current. Although the maximum scale may display
120% or more of rated current and rated voltage in order to make a scale easy
Note
to read, current input is within 100% of rated current.
2. When the display pattern not to display power, reactive power, active energy
and reactive energy is selected, the setting item related to them is skipped.
and the
SET
RESET
Set the set-up menu number to "3". (Set as shown in the right
display.)
+
,
1 Set the current maximum scale.
The maximum scale is set in the range of about 40% to about
+
,
120% of the rated current.
Note: This insturument's rating is 100% value.
The maximum scale value becomes the value in the table on page 50.
2 Set the maximum scale of Active power.
The maximum scale is set in the range of about 40% to about
+
,
120% of the rated full load power.
Note: This insturument's rating is 100% value.
The maximum scale value becomes the value in the table on page 50.
3 Set the single/double deflection of Active power.
+
,
When the + and – are pressed, the scale value of bar graph
flickers at single/double deflection.
4 Set the reactive power maximum scale.
+
,
The setting method is same as that of 2 maximum scale value of active power.
5 Set the power factor scale.
+
,
0.5
According to the set-up diagram (page 13), save the changed
contents or continue to the other set-up menu.
+
,
simultaneously for 2 seconds or more, and the following
0
Set-up Menu 3