4. Set-up

4.9 Simplified Set-up

The setting contents of the main 16 items can be set by using two displays. It is set by the method of substituting the
numerical value.
For the setting contents, refer to the following table.
Simplified setting page: P-1
No.
Content
q
Phase wire
w
Display pattern
e
Using VT/direct input
r
Direct voltage
In the operation mode, press the
operation becomes available.
By pressing
key in the simplified set-up mode, the simplified setting page is changed.
PHASE
Set-up menu
PHASE
DISPLAY
For 1 secend or more
DISPLAY
1 Phase wire
DISPLAY
SET
2 Display pattern
DISPLAY
SET
3 Using VT/
direct input
DISPLAY
SET
4 Direct voltage
DISPLAY
SET
No.
Content
t
VT secondary voltage
y
VT primary voltage
u
CT primary current
i
Time constant for current demand
and the
RESET
SET
Set the set-up menu number to "End". (Set as shown in the right
display.)
+
,
Press the PHASE and the DISPLAY simultaneously for 1 second
or more.
1 Set the phase wire.
+
1 : 3P3W 2CT
,
2 : 3P3W 3CT
3 : 3P4W
2 Set the display pattern.
+
00 : P00
,
to
13 : P13
3 Set the using VT or direct input (without VT).
0 : direct input.
+
,
1 : using VT
4 Set the rated voltage for scaling for the bar graph.
If you set "1: using VT" on set up No.3, this content cannot
be set.
[3P3W]
+
,
1 : 110V
2 : 220V
Simplified setting page: P-2
No.
Content
o
Communication method
!0
ModBus address
!1
ModBus baud rates
!2
ModBus parity
simultaneously for 2 seconds or more, and the following
[3P4W]
1 : 63.5/100V
2 : 100/173V
3 : 110/190V
4 : 220/380V
5 : 240/415V
6 : 254/440V
7 : 277/480V
No.
Content
!3
ModBus stop bit
!4
CC-Link station number
!5
CC-Link baud rates
!6
Communication module reset