  • Page 1 FACTORY AUTOMATION ELECTRONIC MULTI-MEASURING INSTRUMENT ME96SS...
  • Page 2 ME96 Super-S Series ME96 Super-S Series Electronic Indicating Instruments Electronic Indicating Instruments functions and optional units functions and optional units Highly appreciated ME96SS Series Electronic Multi-Measuring Instruments measuring functions and network capability has been released. ME96SSHB-MB (high-performance model) ME96SSHB-MB (high-performance model)
  • Page 3: Table Of Contents

    Remarks MODBUS RTU communication function provided as standard Contents ‡ Outline and Features ............3 ‡ ME96 Super-S Series Ver.B Features ........ 4 ‡ Specifications ..............9 ‡ Operating Instructions ............. 14 ‡ External Dimensions, Installation and Connections ..29 ‡...
  • Page 4: Outline And Features

    Outline and Features Compact size »Realized downsizing for ME96SSEB-MB. It contributes to space saving! 90.2 mm (110.9 mm) 36.0 mm 20.7 mm 13.0 mm ME96SSEA-MB ME96SSEB-MB (Conventional type) (New type) Improved Measurement Functions »Added measurement function, reactive energy, apparent energy, reactive power and apparent power for ME96SSEB-MB. Model name Transmission/Option specifications Main measurement items...
  • Page 5: Me96 Super-S Series Ver.b Features

    ME96 Super-S Series Ver.B Features CC-Link System (With optional plug-in module (ME-0040C-SS96)) »Optimum transmission system for remote monitoring using Mitsubishi PLC. »Contact signals can be remotely monitored by installing the optional module ME-0040C-SS96. This is helpful in wiring and space saving.
  • Page 6 ME96 Super-S Series Ver.B Features Succeeded Display Functions Concurrent Display of 4 items The 4 measured values can be digitally confirmed on one screen. Bar graph display 4 lines of digital display 3 lines of digital display Conventional type New type »Concurrent Display of Each Phase Measured Values...
  • Page 7 Impressive Monitoring Functions Advanced Alarm Display (1) A function to blink the backlight upon occurrence of an alarm is provided. The product has a setting function to blink the backlight upon occurrence of an alarm. (2) The automatic or manual alarm cancel mode can be selected. (3) Up to four points of upper and lower limits can be monitored.
  • Page 8 ME96 Super-S Series Ver.B Features Variety of Complementary Features Password Function With the password function, the following items can be protected from an accidental execution. Password-protected item Password-protected item Shift to the setting mode Adjust the time limit of rolling demand Reset the max./min.
  • Page 9 Test Function »A test function is provided to check the wiring for communication, alarm output/digital output, analog output and pulse output without input of voltage or current. »At the time of wiring test before shipment of the board and counter test for system validation on site, test signals can be output only by applying the auxiliary power. Note: Depending on the optional unit and settings, the test function may not be available (may not be displayed).
  • Page 10: Specifications

    Specifications ‡ME96SSHB-MB Model name ME96SSHB-MB Phase wire system 3-phase 4-wire, 3-phase 3-wire (3CT, 2CT), 1-phase 3-wire, 1-phase 2-wire (common use) Current 5 A AC, 1 A AC (common use) 3-phase 4-wire: max 277/480 V AC 3-phase 3-wire: (DELTA) max 220 V AC, (STAR) max 440 V AC Rating Voltage 1-phase 3-wire: max 220/440 V AC...
  • Page 11 ‡ME96SSRB-MB Model name ME96SSRB-MB Phase wire system 3-phase 4-wire, 3-phase 3-wire (3CT, 2CT), 1-phase 3-wire, 1-phase 2-wire (common use) Current 5 A AC, 1 A AC (common use) 3-phase 4-wire: max 277/480 V AC 3-phase 3-wire: (DELTA) max 220 V AC, (STAR) max 440 V AC Rating Voltage 1-phase 3-wire: max 220/440 V AC...
  • Page 12 Specifications ‡ME96SSEB-MB Model name ME96SSEB-MB Phase wire system 3-phase 4-wire, 3-phase 3-wire (3CT, 2CT), 1-phase 3-wire, 1-phase 2-wire (common use) Current 5 A AC, 1 A AC (common use) 3-phase 4-wire: max 277/480 V AC 3-phase 3-wire: (DELTA) max 220 V AC, (STAR) max 440 V AC Rating Voltage 1-phase 3-wire: max 220/440 V AC...
  • Page 13 ‡Standards Compliance Electromagnetic Compatibility Emissions EN 61326-1 / EN 55011, CISPR 11 Radiated Emission FCC Part15 Subpart B Class A EN 61326-1 / EN 55011, CISPR 11 Conducted Emission FCC Part15 Subpart B Class A Harmonics Measurement EN 61000-3-2 Flicker Meter Measurement EN 61000-3-3 Immunity Electrostatic discharge Immunity...
  • Page 14 SD memory card (EMU4-SD2GB) *1: Be sure to use a SD memory card, EMU4-SD2GB, manufactured by Mitsubishi Electric Corporation. Using a SD memory card not manufactured by Mitsubishi Electric Corporation may cause a trouble such as data corruption in the card or system stop. Regarding the use of commercially available SD memory cards, access our FA website.
  • Page 15: Operating Instructions

    Operating Instructions Functions ‡ Name of each part Function LEAD status Light up when leading reactive energy is measured LAG status Light up when lagging reactive energy is measured »LCD Functions Built-in logging status Light up when the built-in logging function is operating Digital element display Display measuring elements expressed in digital numbers Digital display...
  • Page 16 Operating Instructions Basic Set-up Operations » To access the setting mode, press and hold the buttons down at the same RESET The underlined setting parameters are time for 2 s. Press the button to display the items to be set, and the buttons, the initial value.
  • Page 17 e(2) (2) For measurement with VT eVT/Direct voltage <Secondary voltage settings> (a) 3-phase 4-wire setting (phase voltage) 63.5 V 100 V 110 V 115 V 120 V (b) 3-phase 3-wire (2CT, 3CT) or 1-phase 2-wire setting (line voltage) 100 V 110 V 220 V DISPLAY <Set primary voltage>...
  • Page 18 Operating Instructions <Continued from previous page> eMODBUS RTU eSet the MODBUS RTU communication parity. communication parity DISPLAY even (EVEn) rMODBUS RTU rSet the MODBUS RTU communication stop bit. communication stop bit Stop bit 1 Stop bit 2 DISPLAY Set-up menu Select another set-up menu or end set-up.
  • Page 19 Set-up menu 2: MODBUS TCP Communication settings (when ME-0000MT-SS96 or ME-0040MT2-SS96 is installed) *1 Only for ME96SSHB-MB or ME96SSRB-MB, it is applicable. *2 Only for ME96SSHB-MB, it is applicable. Set-up menu Adjust the set-up menu No. to “2”. qSelect MODBUS TCP communication or MODBUS RTU communication. DISPLAY Mb.tcp : MODBUS TCP communication qCommunication setting...
  • Page 20 Operating Instructions Set-up menu 3: Display settings (active energy, harmonics measurement, etc.) Set-up menu Adjust the set-up menu No. to “3”. DISPLAY qActive/Reactive energy qSet the display combination for imported/exported and lag/lead of active/reactive energy and measurement method the measurement method for reactive energy. Display combinations Reactive energy Combinations...
  • Page 21 eBuilt-in logging Sets whether or not to use the built-in logging function. Use/non-use (Use) (Non-use) DISPLAY rBuilt-in logging Sets a logging item pattern to choose data that are internally logged. item patterns Patterns usable for setting: LP00 LP01 LP02 By selecting LP00, you can freely choose logging items. Logging item patterns for LP01 &...
  • Page 22 Operating Instructions <Continued from previous page> eUse this to set the cycle in which detailed data of the built-in logging item pattern “LP01” or “LP02” are logged. tBuilt-in logging period 15 min 30 min 60 min Set-up menu According to “3.1 Set-up Flow”, either exit from setting or continue setting in any other set-up menu. Set-up menu 6: Analog output setting (only when ME-4210-SS96B is installed) * Only for ME96SSHB-MB or ME96SSRB-MB, it is applicable.
  • Page 23 e(1) eAnalog output CH1 eSet the details for “analog output CH1.” detailed settings (The following settings can be made separately from the measurement items included in the display pattern.) (1) If analog output is selected for current, current demand, voltage, power, reactive power, power factor (set-up menu: 6.6.1) Output item Setting range...
  • Page 24 Operating Instructions Set-up menu 6: Logging setting (only when ME-0000BU-SS96 is installed) * Only for ME96SSHB-MB or ME96SSRB-MB, it is applicable. Set-up menu Adjust the set-up menu No. to “6”. DISPLAY qOptional selection qSelect “optional logging” or “built-in logging” PLUG buiLt (Optional logging) (Built-in logging)
  • Page 25 ‡Operation (for ME96SSHB-MB) »Display Change »Changing Phases Press , the measurement display switches over. Press , the current phase and the voltage phase switches PHASE DISPLAY over. When the buttons are held down for DISPLAY 2 seconds or more, the display will change in reverse order. Example of display switching (Phase wiring system: 3P4W) Example of display switching of measurement screen (Phase wire system: 3-phase 4-wire, Display pattern: P01) DISPLAY...
  • Page 26 Operating Instructions »Changing Upper/Lower Limits for Alarm Activation and Cancellation When measurement values exceed the upper/lower limit values that have been set, an alarm activates and the screen begins to blink. During Alarm Generation » Alarm condition: When a measured value exceeds the alarm value setting, the screen begins to flash and the alarm contact closes. Alarm cancelled: When the alarm is cancelled, the screen stops flashing and the alarm contact opens.
  • Page 27 ■Display Pattern Contents The items set in display patterns and additional settings will be displayed as explained in the following table. »ME96SSHB-MB/ME96SSRB-MB Screen Display (3-phase 4-wire) Screen set based on display pattern Display pattern No.1 No.2 No.3 No.4 No.5 No.6 No.7 No.8 No.9...
  • Page 28 Operating Instructions »ME96SSEB-MB Screen Display (3-phase 4-wire) Screen set based on display pattern Display pattern No.1 No.2 No.3 No.4 No.5 No.6 No.7 No.8 No.9 No.10 line line line line varh line var1 line var2 line var3 line Aavg DAavg W∑ var∑...
  • Page 29 Memo...
  • Page 30: External Dimensions, Installation And Connections

    External Dimensions, Installation and Connections Dimensions ME96SSHB-MB, ME96SSRB-MB ME96SSEB-MB Terminal screw M3 Terminal screw M3 96.0 96.0 Optional Plug-in Module : ME-4210-SS96B, Optional Plug-in Module : Optional Plug-in Module : Optional Plug-in Module : ME-0040C-SS96, ME-0052-SS96 ME-0000BU-SS96 ME-0000MT-SS96 ME-0040MT2-SS96 88.8 88.8 88.8 88.8...
  • Page 31 Wiring 1 Applicable Cable Size Product type Screw type Wire for use Tightening torque ME96SSHB-MB, 0.8 N·m For crimped terminal: AWG 26 to 14 (Connection up to two wires) ME96SSRB-MB Outer diameter Appropriate crimped terminal: One for M3 screw 6.0 mm or less in outer diameter. ME96SSEB-MB 0.5 N·m Single wire, Stranded wire: AWG 24 to 14 (For stranded wire, possible in combination with rod terminals)
  • Page 32 External Dimensions, Installation and Connections Wiring Diagrams (Continued) 1-phase 3-wire system 1-phase 2-wire system: With VT MODBUS RTU T/R+ T/R+ Communication MODBUS RTU T/R- T/R- Communication qAuxiliary power supply MODBUS RTU 100 V AC to 240 V AC or 100 V DC to 240 V DC Communication wFuse (recommendation) Rated current: 0.5 A, Rated breaking...
  • Page 33 Wiring Diagrams (Continued) 1. Pulse output, alarm output, and digital input/output cables must not be in close proximity or bundled with power cables or high-voltage cables. When laid parallel, separate by the distance shown in the following table. Condition Distance Power lines of 600 V AC or less 300 mm or more Other power lines...
  • Page 34: Related Products

    Forms and graphs can be easily prepared by using the spreadsheet software (logging unit utility*). * The logging unit utility can be downloaded for free from Mitsubishi Electric FA site. Realize energy saving with a unit equipped with “control” function Equipped with functions interlocked with measurement value to control equipment automatically.
  • Page 35 ‡EcoMonitorLight Energy measuring unit with integrated display for easily realizing the visualization of energy A three-model line-up: a 3-phase 3-wire system designed for users wanting simple power measurements at low cost; and a 3-phase 4-wire system designed for users looking for basic power measurements plus something extra (harmonic measurements, alarm monitoring, etc.).
  • Page 36: Safety Precautions

    Safety Precautions To ensure safety, read the following items carefully before use and always comply with procedures during use. Special attention should be given to items enclosed in a box and marked “Caution.” Additionally, please carefully read the operations manual supplied with the product before use, and ensure that the manual read by the end user as well.
  • Page 37 Mitsubishi Electric shall not be liable for: Damage that cannot be attributed to Mitsubishi Electric; lost opportunity or earnings resulting from failure of a Mitsubishi Electric product; damage, secondary damage or compensation for an accident resulting from special circumstances regardless of whether or not the circumstances were foreseeable;...
  • Page 38 (MEMO)
  • Page 39 (MEMO)
  • Page 40 Precautions Before Use • Please consult with a Mitsubishi Electric representative when considering the application of products presented in this catalogue with machinery or systems designed for specialized use such as nuclear power, electrical power, aerospace/outer space, medical, or passenger transportation vehicles.