Basic Set-Up Operations - Mitsubishi Electric Super-S ME96SS Series Manual

Electronic multi-measuring instrument
Table of Contents

Advertisement

Operating Instructions

Basic Set-up Operations

»
To access setting mode, press and hold the
for 2s. Press the
button to display the items to be set, and the
SET
the details. Settings can be saved for each set-up menu No. To do so, press the
when the End screen is displayed.
Set-up menu 1: Basic settings (set phase wire system, display pattern, Using VT/direct input, CT primary current, etc.)
Set-up menu
DISPLAY
SET
qPhase/Wire system
DISPLAY
SET
wDisplay pattern
DISPLAY
SET
eVT/Direct voltage
DISPLAY
SET
15
and
SET
Adjust the set-up menu No. to "1".
qSet the phase/wire system according to the number
of measurement circuits targeted.
3P4:
3-phase, 4-wire system
3P3. 2Ct: 3-phase, 3-wire system (2CT)
3P3. 3Ct: 3-phase, 3-wire system (3CT)
1P3. 1n2: 1-phase, 3-wire system (1N2 display)
1P3. 1n3: 1-phase, 3-wire system (1N3 display)
1P2:
1-phase, 2-wire system
wSet the display pattern
: Can be displayed with this setting only
: Other settings are required to display data
: Select P00 and set display order and position
eSet VT
In the case of direct measurements (without VT) = > To select no, press
In the case of using VT = > To select yES, press
·To set Three phase 4-wire
no
yES
·To set Three phase 3-wire or Single phase 2-wire
yES
no
(1) In the case of direct measurements (without VT)
(a) Three phase 4-wire setting (phase voltage/line voltage)
63.5/110V
100/173V
(b) Three phase 3-wire (2CT, 3CT) or Single phase 2-wire setting (line voltage)
110V
220V
440V
(c) Single phase 3-wire setting (1N2, 1N3) (phase voltage/line voltage)
110/220V
220/440V
buttons down at the same time
RESET
and
buttons to set
SET
q
(1) ME96SSHA-MB / ME96SSRA-MB
A
DA
V
W
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P00
(2) ME96SSEA-MB
A
DA
V
W
P01
P02
P03
P04
P05
P06
P07
P08
P09
P00
and see (1) below.
SET
and see (2) below.
SET
<For Single phase 3-wire setting for qPhase/Wire system >
Only used for direct measurements.
Skipped for this setting.
110/190V
220/380V
230/400V
The underlined setting parameters are
the initial value.
button
w
Additional screens
PF Var
VA Hz
Vah
varh
Additional screens
HI/HV
PF
Hz
e
240/415V
254/440V
e (1)
DW
HI/HV
DI/DO
277/480V