3.14 Examples Of Simple Settings - Mitsubishi Electric ME96SSH-MB User Manual

Multi-measuring instrument
Hide thumbs Also See for ME96SSH-MB:
Table of Contents

Advertisement

3.Setting
3.14 Examples of Simple Settings
The following shows a simple setting example.
■Setting Example
Model:
Phase wire system : 3-phase 4-wire
Measuring element :
Input Voltage :220/380V
CT primary current : 200A
CT Secondary current:5A
frequency
MODBUS
■Setting Procedure
Items of which setting value need to be changed are indicated by
Operation mode
Press
Setting menu
SET
Phase wire system
SET
Display pattern
SET
VT/direct voltage
selection
SET
Direct voltage
SET
CT secondary
current
SET
CT primary
current
SET
frequency
SET
Time constant for
rolling
demand
SET
Time constant for
current demand
SET
Setting menu
SET
ME96SSH-MB(Not option unit)
A, V, W, PF
:50Hz
®
RTU:address
1,
baud rates
Note: For more details about setting contents, refer to pages 15 to 20.
RESET
simultaneously for 2seconds
SET
Set the setting menu number to "1" and then press
The factory default setting is "3-phase 4-wire," so just press SET.
Setting is "P01," so just press SET.
The factory default setting is "No VT," so just press SET.
The factory default setting is "220/380V," so just press .
The factory default setting is "5A," so just press SET.
Set to "200A" and then press SET.
The factory default setting is "50Hz," so just press SET.
The factory default setting is "15min/1min," so just press SET.
The factory default setting is "0 second," so just press SET.
Set the setting menu number to "2" and then press SET .
19.2kbps,
parity
even,
stop bit
.
S E T
- 40 -