3. Setting
3.14. Examples of Simple Settings
The following shows a simple setting example.
■Setting Example
Model:
Phase wire system : 3-phase 4-wire
Measuring element :
Input Voltage :220/380V
CT primary current : 200A
CT Secondary current:5A
frequency
MODBUS
■Setting Procedure
Items of which setting value need to be changed are indicated by
Press
Setting menu
SET
SET
SET
VT/direct voltage
selection
SET
Direct voltage
SET
CT secondary
current
SET
CT primary
current
SET
frequency
SET
Time constant for
current demand
SET
Setting menu
SET
ME96SSEA-MB
A, V, W, PF
:50Hz
®
RTU:address
1,
baud rates
Note: For more details about setting contents, refer to pages 16 to 19.
simultaneously for 2seconds
+
Set the setting menu number to "1" and then press
The factory default setting is "No VT," so just press SET.
The factory default setting is "220/380V," so just press .
The factory default setting is "5A," so just press SET.
Set to "200A" and then press SET.
The factory default setting is "50Hz," so just press SET.
The factory default setting is "0 second," so just press SET.
Set the setting menu number to "2" and then press SET .
19.2kbps,
even,
parity
stop bit
.
S E T
34