4. Set-up
4.6 Alarm Set-up
This sets the upper and lower limit alarm. The upper and lower limit set value mark "
the bar graph. From the display items, 4 element can be set.
In the operation mode, press
becomes available.
Set-up menu
DISPLAY
SET
1 Alarm item 1
DISPLAY
SET
2 Alarm value 1
DISPLAY
SET
to
3 Alarm item 2 to 4
DISPLAY
SET
and
simultaneously for 2 seconds or more, and the following operation
SET
RESET
Set the set-up menu number to "5". (Set as shown in the right
display.)
+
,
1 Set the Alarm item to be allowed to measurement items.
Three phase 3-wire
non
A upper limit
A lower limit
Demand A upper limit
Demand A lower limit
V
upper limit
(L-L)
V
lower limit
(L-L)
W upper limit
W lower limit
+
,
var upper limit
var lower limit
PF upper limit
PF lower limit
Hz upper limit
Hz lower limit
Harmonic current total
RMS value
Harmonic voltage total
distortion ratio
Note 1: Even if it is a measurement item not selected by the display pattern, it is possible to select it.
Note 2: The alarm of W, var, and PF is judged from the total RMS value.
Note 3: The upper alarm of A and DA is judged from the phase of 1, 2, 3 and N.
The lower alarm of A and DA is judged from the phase of 1, 2 and 3. (N is excluded.)
Note 4: The alarm of the total distortion ratio is judged from the phase of 1, 2 and 3. (N is excluded.)
2 Set the alarm value of Alarm item 1. The set-up range is as
shown below.
A, DA, A
, DA
N
A,DA lower limit
V upper limit
V lower limit
W, var upper limit
+
,
W, var lower limit
PF upper limit
PF lower limit
Hz upper limit
Hz lower limit
Harmonic current RMS value upper limit
Harmonic voltage total distortion ratio upper limit
Note: An upper and lower limit alarm index by the bar graph is displayed in the step of about 5% though the digital
value can be set in the above-mentioned step on A, DA, V, W and var. However, the alarm is generated with
the accuracy of the digital value.
DA: current demand
V alarm value is set for value of primary voltage (direct voltage).
A, DA, W and var is set for value of rated scale.
+
,
3 Set the upper and lower limit alarm item 2 to 4 (AL2, AL3, AL4) in the same method.
Three phase 4-wire
non
A upper limit
A lower limit
A
upper limit
N
Demand A upper limit
Demand A lower limit
Demand A
V
upper limit
(L-N)
V
lower limit
(L-N)
V
upper limit
(L-L)
V
lower limit
(L-L)
W upper limit
W lower limit
var upper limit
var lower limit
PF upper limit
PF lower limit
Hz upper limit
Hz lower limit
Harmonic current total RMS value
Harmonic current phase N RMS value
Harmonic voltage total distortion ratio
Alarm item
Set-up range
upper limit
5 to 100 to 120%
N
3 to 10 to 95%
25 to 110 to 135%
20 to 70 to 95%
–95 to 100 to 135%
–120 to 3 to 95%
–0.05 to 1 to 0.05
–0.05 to –0.5 to 0.05
45 to 65Hz
45 to 65Hz
5 to 35 to 120%
0.5 to 3.5 to 20%
Set-up Menu 5
(blinking)" is displayed on
Display of non upper
and lower limit alarm
upper limit
N
Display when A upper limit is set
to upper and lower limit alarm
Step
1%
1%
Example display when A
1%
upper limit is set to 100%
1%
1%
1%
0.05
0.05
1Hz
1Hz
1%
0.5%