CHAPTER 4 APPLIED OPERATION

4.3 How to Use Event Input

J Event input
assignments
Multi-SP function
0
1, 2
Run/Stop

Multi-SP

Auto/Manual
SP mode
4--8
• When using event input, mount the option unit (E53-AKB). Up to two
E53-AKB units can be mounted on the E5AK, and two event inputs
can be used for each E53-AKB unit.
E53-AKB × 1 unit
E53-AKB × 2 units : 4 event inputs
• Event inputs can be switched up to 100,000 times.
• You can choose from the following five event input functions:
Multi-SP
Run/Stop
Remote/Local
Auto/Manual
SP mode
• In the case of the multi-SP function, the number of event inputs
(event input 1 or 2) set in the "multi-SP function" parameter (option
mode) are used. When four event inputs are used, the multi-SP func-
tion is automatically assigned to event inputs 1 and 2 for the desig-
nated number. When two event inputs are used, the multi-SP function
is automatically assigned to event inputs 3 and 4 for the designated
number.
• Other functions are assigned to event inputs 1 to 4 not used for the mul-
ti-SP function according to the setting of the "event input assignment 1
to 4" parameters (option mode). However, note that "event input assign-
ment 1/2" parameters cannot be used when only one unit of the
E53-AKB is installed.
Event input
1
0
1
2
• The following table shows the relationship between the settings and
functions of the "event input assignment 1 to 4" parameters.
Setting
Event input disabled
ON : Stop
ON : Remote
ON : Manual
ON : RSP
: 2 event inputs
4 event inputs
2
3
4
Multi-SP
Other event input functions
Function
/OFF : Run
/OFF : Local
/OFF : Auto
/OFF : LSP
2 event inputs
3
4