Assigned Output Functions - Omron E5CZ User Manual

Digital temperature controller with 11-segment display
Hide thumbs Also See for E5CZ:
Table of Contents

Advertisement

Setting Output Specifications
Direct/reverse
orev
operation
or-r
Operation Level
PV/SP
C
30
0
3-5-3

Assigned Output Functions

Example: E5CZ
Parameter name
Symbol
out1
Control output 1
assignment
alm1
Alarm output 1
assignment
alm2
Alarm output 2
assignment
Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Levell
Input type
in-t
5
Initial Setting Level
Standard or
5-hc
heating/cooling
stnd
38
5. Select the "direct/reverse operation" parameter by pressing the M key.
The default is or-r (reverse operation). To select or-d (direct opera-
tion), press the U key.
6. To return to the operation level, press the O key for at least one second.
• Function assignments can be changed by changing the settings for con-
trol and alarm assignments.
• The default function assignments for each output are shown below.
Parameter name
Control output 1 assignment
Alarm output 1 assignment
Alarm output 2 assignment
Alarm output 3 assignment (E5AZ/
EZ only)
• Each output is automatically initialized as shown below by changing the
control mode.
Standard
Control output (heating)
Alarm 1
Alarm 2 (See note.)
Note
For the E5AZ/EZ, alarm 3 is assigned for control output (cooling) (alarm output
2 is assigned for alarm 2).
In this manual, assigned control outputs and alarm outputs are indicated as
follows: "Control output 1 must be assigned" or "Alarm 1 must be assigned."
The following example sets the following control and alarm assignments.
Control output 1: Control output (heating); Alarm output 1: Alarm 1; Alarm out-
put 2: Control output (cooling).
1. Press the O key for at least 3 seconds to move from the operation level
to the initial setting level.
2. Select the "standard or heating/cooling" parameter by pressing the M
key.
Symbol
out1
Control output (heating)
alm1
Alarm 1
alm2
Alarm 2
alm3
Alarm 3
Heating/cooling
Control output (heating)
Alarm 1
Control output (cooling) (See note.)
Section 3-5
Initial status

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cz-uE5ezE5az