Using Event Inputs

4-5

Using Event Inputs

4-5-1

Event Input Settings

Parameter
Number of
0 (See
multi-SP
note.)
uses
1
2
4-5-2

How to Use the Multi-SP Function

Using Event Inputs
• Event inputs can be used for the multi-SP function, starting/stopping oper-
ation (RUN/STOP), and switching between auto/manual.
• Of these, the multi-SP function, event inputs are used only for the number
(0 to 2) set in the "number of multi-SP uses" parameter (advanced func-
tion setting level).
• Event inputs (1 and 2) that are not used for the multi-SP function are
assigned using the "event input assignment 1" and "event input assign-
ment 2" parameters (advanced function setting level).
• Event inputs can be used on the following Controllers:
E5CZ-@2M@@ with E53-CZB or E53-CZHB
E5AZ-@3@M@@ with E53-AZB
E5EZ-@3@M@@ with E53-AZB
Setting
Event input
assignment 1
NONE, STOP, MANU
(Not displayed.)
NONE, STOP, MANU Multi-SP, 2 points
(Not displayed.)
Note
If the "number of multi-SP uses" is set to 0, and both input assignments
1 and 2 can be set. Once "STOP" (RUN/STOP), or "MANU" (auto/manu-
al) has been assigned to one event input, the other event can be as-
signed only to either of the remaining two settings.
E5CZ
EV1
EV2
+
+
When you are setting two externally input set points, set in the "number of
multi-SP uses" parameter.
• Switching is possible between two set points (0 and 1) by setting the
"number of multi-SP uses" parameter to 1.
The default setting is 1 and does not need to be changed to switch
between two set points.
Set point 0 or 1 is specified by the ON/OFF state of event input 1.
The multi-SP function allows you to set up to four set points (SP 0 to 3) in the
adjustment level. The set point can be switched by operating the keys on the
front panel or by using external input signals (event inputs).
Event inputs can be used if the Controller supports the event input function
and if the "number of multi-SP uses" parameter is set to 1 or 2.
Event input
Function of event
assignment 2
None, or switching RUN/STOP, or switching
auto/manual
(switching set points 0
and 1)
Multi-SP, 4 points (switching set points 0, 1, 2,
3)
E5AZ/EZ
EV1
EV2
Section 4-5
Event inputs
Function of event
input 1
None, or switching
RUN/STOP, or auto/
manual
EV1
+
EV1
EV2
+
EV2
input 2
69