Initial Setting Level
in-h
Scaling Upper Limit
in-l
Scaling Lower limit
dp
Decimal Point
Function
Setting
See
See
d-u
Temperature Unit
Function
Setting
See
See
• These parameters can be used when the input type is set for an analog
input.
• When an analog input is used, scaling is performed. Set the upper limit in
the "scaling upper limit" parameter and the lower limit in the "scaling lower
limit" parameter.
• The "decimal point" parameter specifies the decimal point position of
parameters (set point, etc.) whose unit is EU.
• Scaling Upper Limit, Scaling Lower Limit
Parameters
Scaling upper limit
Scaling lower limit + 1 to 9999
−1999 to scaling upper limit − 1
Scaling lower limit
• Decimal Point
Parameters
Decimal Point
Controllers with Thermocouple/Resis-
tance Thermometer Universal-inputs
Controllers with Analog Inputs
Set value
0
0 digits past decimal point
1
1 digits past decimal point
2
2 digits past decimal point
3
3 digits past decimal point
Related Parameters
Input type (initial setting level): Page 119
• Set the temperature input unit to either °C or °F.
Setting range
c: °C, f: °F
c
Related Parameters
Input type (initial setting level): Page 119
The input type must be set for an
analog input.
Setting range
Model
Settings
Example
1234
123.4
12.34
1.234
The input type must be set for a tem-
perature input.
Default
Section 5-6
Unit
Default
None
100
None
0
Setting
Default
range
0 to 1
0
0 to 3
0
121