Adjustment Level
See
See
c-db
Dead Band
Function
Setting
of-r
Manual Reset Value
Function
Setting
See
See
hys
Hysteresis (Heating)
chys
Hysteresis (Cooling)
Function
114
Related Parameters
Proportional band (adjustment level): Page 113
This parameter sets the output dead band width for heating/cooling control. A
negative setting sets an overlapping band.
• This parameter sets an area in which the control output is 0 centering
around the set point for a heating/cooling control.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the "deci-
mal point" parameter setting.
Controllers with Thermocouple/Resis-
tance Thermometer Universal-inputs
Controllers with Analog Inputs
Note
Set "none" as the unit for Controllers with Analog Inputs.
• This parameter sets the required manipulated variable to remove offset
during stabilization of P or PD control.
Setting range
0.0 to 100.0
Related Parameters
Integral time (adjustment level): Page 113
PID ON/OFF (initial setting level): Page 122
This parameter sets the hysteresis for ensuring stable operation at the ON/
OFF switching point.
• For standard control, use the "hysteresis (heating)" parameter. The "hys-
teresis (cooling)" parameter cannot be used.
Model
Setting range
−199.9 to 999.9
−19.99 to 99.99
Unit
Default
%
50.0
Section 5-4
The control system must be set to
heating/cooling control.
Unit
°C or °F
0.0
(See note.)
%FS
0.00
The control must be standard control
and 2-PID control.
The "integral time" parameter must
be set to 0.
The control must be ON/OFF control.
For the "hysteresis (cooling)" param-
eter, the control must be heating/
cooling control.
Default