Omron E5CZ User Manual page 147

Digital temperature controller with 11-segment display
Hide thumbs Also See for E5CZ:
Table of Contents

Advertisement

Initial Setting Level
See
See
cp
Control Period (Heating)
c-cp
Control Period (Cooling)
Function
Setting
See
See
orev
Direct/Reverse Operation
Function
Setting
alt1
Alarm 1 Type
Function
124
Related Parameters
Input type: Page 119, PID ON/OFF: Page 122 (initial setting level), ST stable
range (advanced function setting level): Page 137
• These parameters set the output periods. Set the control periods taking
the control characteristics and the electrical durability of the relay into
consideration.
• For standard control, use the "control period (heating)" parameter. The
"control period (cooling)" parameter cannot be used.
• Whenever the heating control output is a current output, the "control
period (heating)" parameter cannot be used.
• For heating/cooling control, the control period can be set independently
for heating and cooling. The "control period (heating)" parameter is used
for the heating control output, and the "control period (cooling)" parameter
is used for the cooling control output.
Parameters
Control period (heating)
Control period (cooling)
Related Parameters
PID ON/OFF (initial setting level): Page 122
• "Direct operation" refers to control where the manipulated variable is
increased when the process value increases. Alternatively, "reverse oper-
ation" refers to control where the manipulated variable is increased when
the process value decreases.
Setting range
or-r: Reverse operation, or-d: Direct operation
• Select one of the following three alarm 1 types:
Deviation, Deviation range, or Absolute value
The cooling control output and heat-
ing control output must be assigned
to relay/voltage outputs.
The control must be set to 2-PID
control.
For the "control period (cooling)"
parameter, the control must be set to
heating/cooling control.
Setting range
Unit
0.5 or 1 to 99
Second
0.5 or 1 to 99
Second
Alarm 1 must be assigned.
Section 5-6
Default
20
20
Default
or-r

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cz-uE5ezE5az

Table of Contents