Advanced Function Setting Level
See
See
alh1
Alarm 1 Hysteresis
alh2
Alarm 2 Hysteresis
alh3
Alarm 3 Hysteresis
Function
Setting
See
See
hbu
HB ON/OFF
Function
Setting
Related Parameters
Alarm value 2 and 3: Page 102, Alarm value upper limit 2 and 3, Alarm value
lower limit 2 and 3: Page 103 to 104 (operation level)
Alarm 2 to 3 type (initial setting level): Page 126
Alarm 2 and 3 hysteresis: Page 135, Standby sequence reset: Page 133,
Alarm 2 and 3 latch: Page 139 (advanced function setting level)
• These parameters set alarm 1, 2, and 3 hysteresis.
Controllers with Thermocouple/Resis-
tance Thermometer Universal-inputs
Controllers with Analog Inputs
Note
Set "none" as the unit for Controllers with Analog Inputs.
Related Parameters
Alarm value 1 to 3: Page 101 to 102, Alarm value upper limit 1 to 3: Page 103
to 104, Alarm value lower limit 1 to 3: Page 103 to 104 (operation level)
Alarm 1 to 3 type (initial setting level): Page 124 to 126
Standby sequence reset: Page 133, Alarm 1 to 3 open in alarm: Page 134,
Alarm 1 to 3 latch: Page 139 (advanced function setting level)
• Set to use the heater burnout alarm.
on: Enabled, off: Disabled
Models
0.1 to 999.9
0.01 to 99.99
Setting range
Alarm 1 must be assigned, and the
alarm 1 type must not be 0 or 12.
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Setting range
Unit
°C or °F
(See note.)
%FS
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
Default
on
Section 5-7
Default
0.2
0.02
135