Performing Manual Control
Press O key for at least 1 s.
Manual Control Level
C
25
20
PV/MV
Auto/Manual Select
Addition
86
a-m
Press O key for at least
3 s.
a-m display flashes for
at least 1 s.
• If an event input is set to "MANU" (auto/manual), the "auto/manual switch"
parameter will not be displayed. Use the event input to switch between
automatic and manual modes.
• The "auto/manual select addition" parameter must be set to ON in the
advanced function setting level before it is possible to move to manual
mode. The default is OFF.
Note
(1) Priority of Manual MV and Other Functions
Even when operation is stopped, the manual MV is given priority.
Auto-tuning and self-tuning will stop when manual mode is entered.
(2) Manual MV and SP Ramp
If operating, the SP ramp function will continue even when manual mode
is entered.
Operation Level
C
25
PV
M
C
25
PV/SP
100
M
a-m
Auto/manual switch
M
m-sp
Multi-SP
0
M
Section 4-12