Initial Setting Level
o1-t
Linear Current Output
Function
Setting
See
See
amov
Move to Advanced Function Setting Level
Function
See
See
128
This parameter selects the output type for linear current outputs.
• Select either 4 to 20 mA or 0 to 20 mA when control output 1 is a current
output.
Linear current
output
4-20: 4 to 20 mA
0-20: 0 to 20 mA
Note
Even when control output 1 is used as a control output or a simple transfer
output, 0 to 20 mA can be used.
Related Parameter
Transfer output type (initial setting level): Page 127
• Set the "move to advanced setting level" parameter set value to "−169."
• Move to the advanced setting level either by pressing the M key or O
key or by waiting for 2 seconds to elapse.
Related Parameter
Initial setting/communications protect (protect level): Page 96
A current output must be assigned.
Default
4-20
The "initial setting/communications
protect" parameter must be set to 0.
Section 5-6