Omron E5CZ User Manual page 148

Digital temperature controller with 11-segment display
Hide thumbs Also See for E5CZ:
Table of Contents

Advertisement

Initial Setting Level
Setting
Set values
0
Alarm function OFF
1 (See note
Upper- and lower-limit
1.)
2
Upper-limit
3
Lower-limit
4 (See note
Upper- and lower-limit
1.)
range
5 (See note
Upper- and lower-limit
1.)
with standby sequence
6
Upper-limit with standby
sequence
7
Lower-limit with standby
sequence
8
Absolute-value upper-
limit
9
Absolute-value lower-
limit
10
Absolute-value upper-
limit with standby
sequence
11
Absolute-value lower-
limit with standby
sequence
12
LBA (alarm 1 type only)
Note
(1) With set values 1, 4 and 5, the upper- and lower- limit values can be set
independently for each alarm type, and are expressed as "L" and "H."
(2) Set value: 1 (Upper- and lower-limit alarm)
Case 1
L
H
SP
H < 0, L > 0
|H| < |L|
(3) Set value: 4 (Lower limit range)
Case 1
L
H
SP
H < 0, L > 0
|H| < |L|
(4) Set value: 5 (Upper- and lower-limit with standby sequence)
Alarm type
When alarm value
X is positive
Output OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
See note 5.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
---
Case 2
Case 3 (Always ON)
H
SP
SP
L H
H > 0, L < 0
H
L
SP
|H| > |L|
SP
H
Case 2
Case 3 (Always OFF)
H
SP
L
SP
L
H
H > 0, L < 0
|H| > |L|
H
L
SP
SP
H
Section 5-6
Alarm output operation
When alarm value
X is negative
See note 2.
L H
SP
X
X
ON
OFF
SP
SP
X
ON
OFF
SP
SP
See note 3.
L H
SP
See note 4.
L H
SP
X
X
ON
OFF
SP
SP
X
ON
OFF
SP
SP
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
H < 0, L < 0
L
H < 0, L > 0
|H|
|L|
H > 0, L < 0
|H|
|L|
L
H < 0, L < 0
H < 0, L > 0
|H|
|L|
H > 0, L < 0
|H|
|L|
L
X
X
X
0
X
0
X
0
X
0
125