Advanced Function Setting Level
Setting
See
See
rest
Standby Sequence Reset
Function
Setting
See
See
Setting range
s: EU/s, m: EU/min
Related Parameters
Set point during SP ramp (operation level): Page 100
SP ramp set value (adjustment level): Page 116
• This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, or advanced function setting level.
• Condition A
Control started (including power ON), and set point, alarm value (alarm
value upper/lower limit), or input shift value (upper/lower-limit temperature
input shift value) changed.
• Condition B
Power ON
• The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
Alarm
(after change)
Alarm
Alarm output:
Condition A
Alarm output:
Condition B
Setting range
a: Condition A, b: Condition B
Related Parameters
Alarm 1 to 3 type (initial setting level): Page 124 to 126
Alarm 1 to 3 latch (advanced function setting level): Page 139
m
The alarm 1/2/3 type must be set to a
type with a standby sequence.
Condition A only
SP change
Condition A
only
a
Section 5-7
Default
Alarm hysteresis
: Standby sequence canceled
: Standby sequence reset
Default
133