Advanced Function Setting Level
ev-m
Number of Multi-SP Uses
Function
Setting
Multi-SP is a function for setting set points 0 to 3 in advance, and switching
between these set points using the ON/OFF combinations of event inputs 1
and 2.
The "number of multi-SP uses" parameter is used when the number of preset
set points is either two or four.
This parameter determines whether the "event input assignment 1" and
"event input assignment 2" parameters are displayed.
The "number of multi-SP uses" parameter displays which functions are
assigned to event inputs 1 and 2.
Number of
0 (See
multi-SP
note. )
uses
1
2
Note
If the "number of multi-SP uses" parameter is set to 0, both input assign-
ments 1 and 2 can be set. Once "STOP" (RUN/STOP), or "MANU" (auto/
manual) has been assigned to one event input, the other event can be
assigned only to either of the remaining two settings.
• Default: 1
Multi-SP switching by event inputs can be used with Controllers that have
event inputs, when the "number of multi-SP uses" parameter is set to 1 or 2.
The following tables show the relationships between ON/OFF combinations of
event inputs 1 and 2 and selected set points.
Number of Multi-SP Uses: 1
Event input 1
OFF
ON
Number of Multi-SP Uses: 2
Event input 1
OFF
ON
OFF
ON
Note
Event inputs can be used on the following Controllers. E5CZ-@2M@@ with
E53-CZB or E53-CZHB E5AZ-@3@M@@ with E53-AZB E5EZ-@3@M@@
with E53-AZB Turn the event inputs ON or OFF while the power is turned
ON. Event input ON/OFF changes are detected for inputs of 50 ms or longer.
Settings
Event input
Event input
assignment 1
assignment 2
NONE, STOP, MANU
(Not dis-
NONE, STOP,
played.)
MANU
(Not displayed.)
Selected set point
Set point 0
Set point 1
Event input 2
OFF
Set point 0
OFF
Set point 1
ON
Set point 2
ON
Set point 3
Section 5-7
Event inputs must be supported.
Event inputs
Function of
Function of
event input 1
event input 2
None, or switching RUN/
STOP, or auto/manual
Multi-SP, 2
None, or
points (switch-
switching
ing set points
RUN/STOP,
0 and 1)
or auto/man-
ual
Multi-SP, 4 points (switching
set points 0, 1, 2, 3)
Selected set point
131