Floor Loading; Clearances - Eaton Powerware 9355 Parallel User Manual

Parallel ups 10/15 kva
Table of Contents

Advertisement

UPS SETUP

Floor Loading

When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table.

Clearances

The following clearances are recommended for the Powerware 9355
UPS:
From Front of Cabinet
From Back of Cabinet
8
EATON Powerware
Standard Model Floor Loadings (2-High/3-High Cabinets)
Powerware 9355
2-High UPS
3-High UPS-32
3-High UPS-64
2-High EBM
3-High EBM
36" (91.4 cm) working space
6" (15.2 cm)
®
9355 Parallel UPS (10/15 kVA) User's Guide
Maximum
Point Loading
Weight
lb/in
381 lb (173 kg)
587 lb (266 kg)
619 lb (281 kg)
480 lb (218 kg)
710 lb (322 kg)
S
164201601 Rev A www.powerware.com
2
2
(kg/cm
)
95 (6.7)
147 (10.3)
155 (10.9)
120 (8.4)
178 (12.5)