OPERATION

User Settings

The following table displays the options that can be changed by the
user.
NOTE Changes to the output voltage or frequency options should be made before turning
on the UPS; otherwise, the changes do not take effect.
Table 3. User Settings
Description
Set Date and Time
Display Contrast
Change Language
Set NominalOutput Voltage
Relay Config
Signal Inputs
Serial Port Config
Modem Config
44
EATON Powerware
Available Settings
Set Month
Date: mm/dd/yyyy
Time: 24:00
Adjust contrast with up/down arrow buttons
Select Language: <English>
Elegir idioma <Español>
Output:
[120V/208V] [127V/220V]
Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or
[X-Slot 2-1/2/3/4]
Setup: [Battery Low] [On Battery] [On
Bypass] [UPS ok] [custom] [empty]
[empty] [Logic]
Signal Input must be wired to the CAN Bridge
Card (see Figure 24 on page 30).
For more information, refer to "Programmable
Signal Inputs" in the Powerware 9355 UPS
(10/15 kVA) User's Guide.
Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
Modem Installation
Set Modem Call Events
Set Modem Init String
Set Modem Call Command
Set Modem Communication Password
®
9355 Parallel UPS (10/15 kVA) User's Guide
Default Setting
01/01/2003
00:00
Moderate
English
120V/208V
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
<empty>
19200
<Not Installed>
Event #0
Call modem: no
ATZ0
None
None
S