Floor Loading

Clearances

8
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide
When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table.
Standard Model Floor Loadings (2-High/3-High Cabinets)
Eaton 9355 UPS
2-High UPS
3-High UPS-32
3-High UPS-64
2-High EBM
3-High EBM
The following clearances are recommended for the Eaton 9355 UPS
UPS:
From Front of Cabinet
From Back of Cabinet
Maximum
Weight
381 lb (173 kg)
587 lb (266 kg)
619 lb (281 kg)
480 lb (218 kg)
710 lb (322 kg)
36" (91.4 cm) working space
6" (15.2 cm)
S
164201601 Rev D www.eaton.com/powerquality
Point Loading
2
2
lb/in
(kg/cm
)
95 (6.7)
147 (10.3)
155 (10.9)
120 (8.4)
178 (12.5)