OPERATION
Restarting the Parallel System
To restart the parallel system:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Press the
50
EATON Powerware
Verify that all UPS breakers on the parallel tie cabinet are in the OFF
position.
Switch on utility power where the UPSs are connected.
Wait for the front panel LCD to illuminate.
The
indicator flashes on each UPS.
Switch all battery circuit breakers to the ON position.
The
indicator stops flashing on each UPS.
Switch the UPS breakers on the parallel tie cabinet to the ON
position.
Verify that no alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
ESC
Press the
button once and then press the
the TURN UPS ON/OFF menu.
Press the button to select the System On option; press the
button.
Confirm the selection. Press and hold the
seconds, until the UPS stops beeping.
The UPS goes to Bypass mode for five seconds, and then the
indicator illuminates. Each UPS should be in Normal mode.
ESC
button until the Eaton Powerware logo appears.
®
9355 Parallel UPS (10/15 kVA) User's Guide
button to select
button for three
S
164201601 Rev A www.powerware.com