Table 3. User Settings (continued)
Description
Start Screen
User Password
Audible Alarms
Battery Charging
Automatic Battery Tests
Full Power Battery Test
Number of Battery Strings
Battery Capacity
Battery Low Alarm Level
Bypass Voltage High Limit
Bypass Voltage Low Limit
Nominal Output Frequency
Synchronization
Synchronization Window
Unsynchronized Transfer to Bypass
Output Frequency Slew Rate
Usage of Bypass
Transfer to Bypass When Overload
Automatic Start Delay
Control Commands from X-Slot1
Control Commands from X-Slot2/Serv
®
EATON Powerware
9355 Parallel UPS (10/15 kVA) User's Guide
Available Settings
Eaton Powerware logo
Mimic screen
Enabled/Disabled
If Enabled is selected, the password is USER.
Normal Sound/Disabled
ABM cycling/constant
Enabled/Disabled
Enabled automatically runs the battery test
once a month.
Enabled/Disabled
0 through 22
(see "Configuring the UPS for EBMs" on
page 47)
1 through 65535 watts per cell
1.750 through 1.950 volts per cell
+1 through +20% (1% increments)
-1 through -20% (1% increments)
50 Hz or 60 Hz
Enabled/Disabled
±0.5 through ±3.0 Hz
(0.1 Hz increments)
Allowed/Not Allowed
0.1 though 5 hertz per second
(0.1 Hz increments)
Enabled/Disabled
After a delay/Immediately
-1 through 32767 seconds
(-1 means disabled)
Allowed/Disabled
Allowed/Disabled
S
164201601 Rev A www.powerware.com
OPERATION
Default Setting
Eaton Powerware logo
Disabled
Normal Sound
ABM cycling
Enabled
Enabled
2 strings for UPS-32 models
4 strings for UPS-64 models
34 W/cell
1.880 V/cell
120V +10%
120V -15%
60 Hz
Enabled
±2.0 Hz
Not Allowed
0.5 Hz/s
Enabled
After a delay
0s
Allowed
Allowed
45