Page 5
Special Symbols The following are examples of symbols used on the product to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions.
During brownouts, blackouts, and other power interruptions, batteries provide emergency power to safeguard operation. With the Eaton 9355 UPS, you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment. Figure 1 shows the Eaton 9355 UPS and an optional Extended Battery Module (EBM).
Page 10
The parallel system consists of two to four UPSs, each with a parallel CAN Bridge Card, and a parallel tie cabinet. Refer to the Eaton 9355 Parallel UPS (10/15 kVA) User's Guide for more information.
Keep unauthorized personnel away from batteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Never dispose of batteries in a fire. Batteries may explode when exposed to flame. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 12
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los requisitos pertinentes. Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 14
Safety Warnings This page intentionally left blank. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
3-High EBM 710 lb (322 kg) 178 (12.5) Clearances The following clearances are recommended for the Eaton 9355 UPS: From Front of Cabinet 36" (91.4 cm) working space 6" (15.2 cm) without PDM installed; with PDM installed, From Back of Cabinet...
Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet. Remove the three M10 bolts securing the rear shipping pad to the pallet and remove the shipping pad. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 17
Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue rolling the cabinet down the pallet until the cabinet touches the floor (see Figure 4). If needed, adjust the leveling feet so that the cabinet rolls freely. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 18
With the cabinet supported, slowly pull the pallet away from the cabinet (see Figure 5). Figure 5. Removing the Pallet 10. Roll the cabinet to the desired location. 11. Continue to “Selecting an Installation Option” on page 13. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Remove the three M10 bolts securing the rear shipping pad to the pallet and remove the shipping pad (see Figure 8). Note: Hold the back of the cabinet so that the bolts can be removed easily without the cabinet rolling backward. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 20
Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue rolling the cabinet down the pallet until the cabinet touches the floor (see Figure 9). If needed, adjust the leveling feet so that the cabinet rolls freely. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
11. Roll the cabinet to the desired location. 12. Continue to the following section, “Selecting an Installation Option. ” Selecting an Installation Option You are now ready to install the Eaton 9355 UPS. Select one of the following installation options according to your UPS configuration: UPS Configuration...
Page 22
UPS Setup This page intentionally left blank. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
To accommodate the feature of easy system expandability, it is recommended that initial installation of the Eaton 9355 UPS contain wiring to support the maximum capacity of the UPS cabinet. Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there is no power.
Page 24
Remove the UPS wiring access cover and one of the conduit landing plates and retain (see Figure 11). Punch two holes in the conduit landing plate for the input and output conduit using a Greenlee punch or ® similar device. Proceed to Step 12. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 25
Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. If the optional input transformer is installed, an input neutral is not required. Note: The Eaton 9355 UPS is a single-feed UPS only. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 26
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW2, TW, THW, THHW, THW2. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 27
13. For UPS only installations, replace the UPS wiring access cover and conduit landing plate. For UPS installations with an input isolation transformer, replace the transformer wiring access cover. 14. Continue to “Stabilizing the Cabinet” on page 43 to complete the UPS installation. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Figure 26 and Figure 27 beginning on page 29 show the oneline diagrams. WARNING Only qualified service personnel (such as a licensed electrician) should perform the UPS installation. Initial startup must be performed by an authorized Eaton Customer Service Engineer. Risk of electrical shock. To hardwire the bypass cabinet: Verify that the electrical connections to the installation site have been properly installed.
Page 32
Greenlee punch or similar device. Verify that the bypass breaker is in the OFF position (see Figure 20). Mount the bypass cabinet to the wall and install the conduit. Figure 20. Version 1 Bypass Breaker Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 33
Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. If the optional input transformer is installed, an input neutral is not required. Note: The Eaton 9355 UPS is a single-feed UPS only. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 34
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW2, TW, THW, THHW, THW2. Maintenance Bypass Contacts Ground Figure 22. UPS Terminal Block (3-High Shown) Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 35
Connect the black and the red wire to TB2 on the UPS. Cap the blue wire. Note: The maintenance bypass contacts are normally-open. To ensure proper bypass operation, DO NOT use the blue wire (it is normally-closed). Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 36
17 . Replace the UPS wiring access cover and conduit landing plate. Maintenance Bypass Wiring to UPS TB2 Ground Neutral Line 1 Line 2 Line 3 Figure 24. Version 1 Load Connections Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 37
Auxiliary Contacts Blue Wire (closed when breaker is open) 225A Bypass Input 80A (4X) LOAD From UPS 1 Output Not Used Not Used Not Used Figure 26. Version 1 Bypass Wiring Diagram Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 38
Version 1 Wall-Mounted Bypass Switch Installation Figure 27. UPS with Input Isolation Transformer and Version 1 Wall Mounted Bypass Cabinet Wiring Diagram Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Figure 37 through Figure 39 beginning on page 40 show the oneline diagrams. WARNING Only qualified service personnel (such as a licensed electrician) should perform the UPS installation. Initial startup must be performed by an authorized Eaton Customer Service Engineer. Risk of electrical shock. To hardwire the bypass cabinet: Verify that the electrical connections to the installation site have been properly installed.
Page 40
Version 2 Wall-Mounted Bypass Switch Installation Front Cover Door Latch Door Figure 28. Version 2 Bypass Cabinet Front Door and Cover Internal Cover Front Cover Figure 29. Version 2 Bypass Cabinet Front Cover Open Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 41
Version 2 Wall-Mounted Bypass Switch Installation Remove the internal cover to gain access to the breakers (see Figure 30). Internal Cover Figure 30. Version 2 Bypass Cabinet Internal Cover Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 42
Verify that the bypass breaker is in the OFF position (see Figure 31). 10. Mount the bypass cabinet to the wall and install the conduit. Figure 31. Version 2 Bypass Cabinet Bypass Breaker Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 43
Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. If the optional input transformer is installed, an input neutral is not required. Note: The Eaton 9355 UPS is a single-feed UPS only. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 44
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW2, TW, THW, THHW, THW2. Maintenance Bypass Contacts Ground Figure 33. UPS Terminal Block (3-High Shown) Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 45
Connect the black and the red wires from the terminal block on the Tie Cabinet to TB2 on the UPS. Note: The maintenance bypass contacts are normally-open. To ensure proper bypass operation, DO NOT use the blue wire (it is normally-closed). Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 46
18. Replace the UPS wiring access cover and conduit landing plate. Line 1 Line 2 Line 3 Neutral Ground Maintenance Bypass Wiring to UPS TB2 Figure 35. Version 2 Bypass Cabinet Load Connections Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 47
20. Verify the phase rotation for each UPS and the bypass input. 21. Reinstall the internal cover. 22. Reinstall the bypass cabinet front cover. 23. Continue to “Stabilizing the Cabinet” on page 43 to complete the UPS installation. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 48
225A Bypass Input 110A (4X) 80A (4X) LOAD From UPS 1 Output 225A Not Used Not Used Not Used Figure 38. Version 2 Bypass Cabinet Bypass Wiring Diagram – with MIS Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 49
Version 2 Wall-Mounted Bypass Switch Installation Figure 39. UPS with Input Isolation Transformer and Version 2 Wall Mounted Bypass Cabinet Wiring Diagram Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 50
Version 2 Wall-Mounted Bypass Switch Installation This page intentionally left blank. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Chapter 7 Stabilizing the Cabinet Note: For seismic installations, you MUST order and install an Eaton 9355 UPS seismic kit; do not use the following instructions. Note: For non-seismic installations, you MUST install the stabilizing bracket on all 3-high cabinets. The stabilizing bracket is optional for 2-high cabinets.
Page 52
Stabilizing the Cabinet M4 Screws Figure 41. Stabilizing Bracket with One Cabinet M4 Screws Figure 42. Stabilizing Bracket with Two Cabinets Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 53
Stabilizing the Cabinet M4 Screws Figure 43. Stabilizing Bracket with Three Cabinets Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 54
Stabilizing the Cabinet This page intentionally left blank. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 56
After UPS startup, ensure maximum battery runtime by configuring the UPS for the correct number of EBMs (see page 67). Front Ground Strap Figure 45. Front Ground Strap Installation (2-High Cabinets Shown) Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
X-Slot Communication Bay #1 Signal Input 1 X-Slot Communication Bay #2 Signal Input 2 REPO (normally open) REPO (normally closed) DB-9 Communication Port Relay Output Contacts Figure 46. Communication Options and Control Terminals Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
On the bottom cover (and also the middle cover if 3-high), remove a knockout tab in the top edge of the cover for each cable: With wire cutters, cut either side of the tab and twist down to remove the tab (see Figure 49). Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 59
Continue to “Operation” on page 61 to start up the UPS. Note: After UPS startup, ensure maximum battery runtime by configuring the UPS for the correct number of EBMs (see page 67). Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Communication Communication Options The Eaton 9355 UPS has serial communication capabilities through the DB-9 communication port or through an X-Slot card in one of the available bays. In addition, the LanSafe Power Management Software can be installed and used to communicate with the UPS via one of the serial communication connections.
X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Eaton 9355 UPS has two available communication bays for any X-Slot card, including: Power Xpert Gateway Card - provides a data gateway from the UPS to the Power Xpert Software; provides ®...
Figure 53 shows an RMP. Figure 54 shows the enclosure dimensions and cable exit openings. Cable Exit Opening for 1/2” Conduit or Provided Strain Relief Horn Silence Button Figure 53. Remote Monitor Panel Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 63
IRC (see Figure 56) and the RMP . Connect the wiring between the RMP and the IRC plug–in terminal blocks using terminations shown in Table 5. See Figure 55 and Figure 56 for plug–in terminal block locations. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
UPS or power information. If there is a power outage and the Eaton 9355 UPS battery power becomes low, LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
UPS running. Maximum resistance is 10 ohm. Note: Leave the REPO connector installed in the REPO port on the UPS rear panel even if the REPO function is not needed. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
If active, the UPS knows that the batteries are disconnected. Building Alarm 1-6 These alarms can be activated separately or at the same time with other building alarms. Not in Use Default Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 68
On Generator If active, the UPS knows that input is fed from the generator. Bypass is disabled; the automatic battery test is disabled. External Transformer Overtemperature This option is not used. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Chapter 10 Operation This chapter contains information on how to use the Eaton 9355 UPS, including front panel operation, UPS startup and shutdown, and configuring the UPS for Extended Battery Modules (EBMs). Control Panel Functions The UPS has a four-button graphical LCD with backlight. It provides useful information about the UPS itself, load status, events, measurements, and settings (see Figure 58).
Operation Initial Startup Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, or the warranty terms as specified on page 79 become void. This service is offered as part of the sales contract for the UPS. Contact service in advance (usually a two-week notice is required) to reserve a preferred startup date.
If an optional isolation transformer is installed, switch the input circuit breaker to the ON position (see Figure 12 on page 17). Switch on utility power where the UPS is connected. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Switch the bypass breaker to the ON position. The load is now powered by utility power. To transfer the load to the UPS, see “Using the Wall-Mounted Bypass Cabinet” on page 71. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Switch the UPS battery circuit breaker to the OFF position. The UPS disconnects from the batteries and is on logic power only. Switch off utility power where the UPS is connected. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 76
Operation This page intentionally left blank. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead–acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Turn the maintenance bypass switch to the BYPASS position. The battery circuit breaker trips, and the UPS is now bypassed, with the load powered by utility power. The UPS automatically shuts down. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
If present, switch the maintenance isolation breaker (MIS) on the wall-mounted bypass cabinet to the ON position; otherwise, switch the UPS breakers (may be designated MOB or UPS) on the wall-mounted bypass cabinet to the ON position. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 80
Transfer the UPS to Normal mode: Press the button to select the Go To Normal Mode option. Press the button until the Eaton logo appears. The UPS is now powering the load in Normal mode. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
32.2" x 12" x 30.3" (81 x 30 x 77 cm) 480 lb (218 kg) 3-High EBM 47.8" x 12" x 30.3" (121.5 x 30 x 77 cm) 710 lb (322 kg) Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 82
<5% THD nonlinear load Output Frequency 50/60-Hz selectable or autoconfiguring Output Frequency Synchronization to line Regulation 101110% for 10 minutes 111125% for 60 seconds 126149% for 5 seconds Output Overload >150% for 300 milliseconds Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 83
ABM technology increases battery service life, optimizes recharge time, and provides a warning Performance before the end of useful battery life Protection Extended Battery Module output protected by 100A circuit breaker Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 84
64 Internal UPS Load Batteries (1) EBM-96 (2) EBM-96 (3) EBM-96 15 kVA/13.5 kW 10 kVA/9 kW NOTE Battery times are approximate and vary depending on the load configuration and battery charge. Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Chapter 13 Troubleshooting The Eaton 9355 UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user. Use the following troubleshooting chart to determine the UPS alarm condition.
Please have the following information ready when you call for service: Model number Serial number Firmware version number Date of failure or problem Symptoms of failure or problem Customer return address and contact information Eaton 9355 UPS (10/15kVA) User’s Guide 164201594—Rev G www.eaton.com/powerquality...
Page 87
“Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts, and labor, as applicable), at the option of Eaton.
Page 88
OTHER LIMITATIONS: Eaton's obligations under this Warranty are expressly conditioned upon receipt by Eaton of all payments due to it (including interest charges, if any). During such time as Eaton has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Eaton shall have no obligation under this Warranty.