UPS SETUP

Floor Loading

Clearances

8
EATON Powerware
When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table.
Standard Model Floor Loadings (2-High/3-High Cabinets)
Powerware 9155
2-High UPS
3-High UPS
3-High UPS with
Isolation
Transformer
2-High EBM
3-High EBM
The following clearances are recommended for the Powerware 9155
UPS:
From Front of Cabinet
From Back of Cabinet
®
9155 Parallel UPS (8–15 kVA) User's Guide
Maximum
Point Loading
Weight (lb)
(lb/in
352
590
148
558
140
480
120
710
178
36" (91.4 cm) working space
6" (15.2 cm)
S
164201592 C www.eaton.com/powerquality
Distributed
2
)
Loading (lb/ft
88
166
278
263
226
335