UPS SETUP

Floor Loading

Leveling Feet (4x)
10.43"
(265 mm)
8.15"
(207 mm)
1.14"
(29 mm)

Clearances

16
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table. Figure 4 shows the leveling feet and casters.
Eaton 9355-F47
Maximum Weight
Unirom
(without Batteries or
Ultracapacitor)
UPS
190 lb (86.2 kg)
Casters (6x)
18.62"
(473 mm)
22.28"
(566 mm)
Figure 4. Leveling Feet and Casters
The following clearances are recommended for the Eaton 9355-F47
Unirom UPS:
From Front of Cabinet
From Back of Cabinet
Standard Model Floor Loadings
Maximum Weight
(with Both Battery
Trays or Ultracapacitor)
410 lb (186 kg)
9.31"
(236.5 mm)
36" (91.4 cm) working space
6" (15.2 cm)
S
164201642 Rev C www.eaton.com/powerquality
Point Loading
2
2
lb/in
(kg/cm
)
103 (7.3)
1.83"
(46.5 mm)