Net B Status Indicator
Status
Off
Flashing
Green
Adapter Diagnostic Items in Single Drive Mode
The following diagnostic items can be accessed using DriveExplorer
(version 3.01 or higher).
No.
Name
1
Reserved
2
Logic Cmd
3
Reference
4
Reserved
5
Logic Sts
6
Feedback
7 – 22 Reserved
23
DSI Overrun Errs
24
DSI Framing Errs
25
DSI CRC Errs
Cause
The adapter is not
powered, or is not
transmitting on the
network.
The adapter is transmitting
on the network.
Description
Logic Command being transmitted to the drive by the adapter.
Reference being transmitted to the drive by the adapter.
Logic Status being received from the drive by the adapter.
Feedback being received from the drive by the adapter.
The number of DSI receive overrun errors.
The number of DSI receive framing errors.
The number of DSI receive CRC errors.
Troubleshooting
Corrective Actions
If Net A indicator is off:
• Securely connect the adapter to the drive
using the Internal Interface (ribbon) cable and
to the network using an Ethernet cable.
• Correctly connect the Ethernet cable to the
Ethernet connector.
• Set a unique IP address using a BOOTP
server or by disabling BOOTP and using
adapter parameters.
If Net A indicator is solid red:
• Configure the adapter to use a unique IP
address and cycle power.
If Net A indicator is flashing red:
• Check the IP address in the adapter and
scanner.
• Ping the adapter.
Normal condition if the adapter is idle.
No action required.
8-5