Allen-Bradley 22-COMM-E FRN 1.xxx User Manual page 92

Ethernet/ip adapter
Table of Contents

Advertisement

8-10
Troubleshooting
Code Event
43
EN Open
44
EN Close
45
EN Timeout
46
EN Comm Flt
47
EN Idle Flt
48
PCCC IO Open
49
PCCC IO Close
50
PCCC IO Time Flt The adapter has not received a PCCC Control message for
51
EN Sent Reset
52
Msg Ctrl Open
53
Msg Ctrl Close
54
Msg Ctrl Timeout
55 – 59 Reserved
60
BOOTP Response The adapter received a response to its BOOTP request.
61
E-mail Failed
Description
An I/O connection from the network to the adapter was opened.
An I/O connection from the network to the adapter was closed.
An I/O connection from the network to the adapter has timed
out.
The adapter has performed the "Comm Flt" action specified
by the user.
The adapter has performed the "Idle Flt" action specified by
the user.
The adapter has begun receiving PCCC Control messages
(the PCCC Control Timeout was previously set to a
non-zero value).
The device sending PCCC Control messages to the adapter
has set the PCCC Control Timeout to a value of zero.
longer than the PCCC Control Timeout.
The adapter received a reset from the network.
The adapter has begun receiving Client-Server Control
messages (the Client-Server Control Timeout was
previously set to a non-zero value).
The device sending Client-Server Control messages to the
adapter has set the Client-Server Control Timeout to a value
of zero.
The adapter has not received a Client-Server Control
message for longer than the established timeout period.
Adapter-Specific Events
The adapter attempted to send an e-mail notice, but could
not deliver the message to the mail server.