PCCC Object
(Continued)
The adapter supports the following PCCC command types:
CMD
FNC
Description
0x06
0x03
Identify host and some status
0x0F
0x67
PLC-5 typed write
0x0F
0x68
PLC-5 typed read
0x0F
0x95
Encapsulate other protocol
0x0F
0xA2
SLC 500 protected typed read with 3 address fields
0x0F
0xAA
SLC 500 protected typed write with 3 address fields
0x0F
0xA1
SLC 500 protected typed read with 2 address fields
0x0F
0xA9
SLC 500 protected typed write with 2 address fields
0x0F
0x00
Word range read
0x0F
0x01
Word range write
See DF1 Protocol and Command Set Manual, Allen-Bradley Publication
No. 1770-6.5.16.
N-Files
N-File
Description
N40
This N-file lets you use Emulated Block Transfer messages to read and write
many types of DPI messages. To use Emulated Block Transfer messages,
you send a Write message to N40:0 – N40:63, wait until the adapter
responds with a reply message, and then read the response data in N40:0 –
N40:63 with a Read message.
For details about Block Transfer messages and the data required for each
byte in the N-File, refer to the Remote I/O Adapter User Manual, Publication
20COMM-UM004....
Bits 15 to 8 are the Most Significant Byte. Bits 7 to 0 are the Least Significant
Byte.
Write
Bits 15
N40:0
0x00
N40:1
DPI Port
N40:2
0x00
N40:3
CIP Class
N40:4
CIP Instance
N40:5
CIP Attribute
N40:6
Data
(length varies based on message)
N40:63
(1)
Use the following DPI Port Assignment table to determine the value for the DPI port.
Length (in Bytes) 0x00
(1)
0x81
CIP Service
EtherNet/IP Objects
Read
0 15
Length (in Bytes)
Status Size
Data
(length varies based on message)