MOD Status Indicator

Status
Cause
Off
The adapter is not powered or
properly connected to the
drive.
Flashing
The adapter has failed the
Red
firmware test.
Solid
The adapter has failed the
Red
hardware test.
Flashing
The adapter is operational,
Green
but is not transferring I/O data.
Solid
The adapter is operational
Green
and transferring I/O data.
Troubleshooting
Corrective Action
• Securely connect the adapter to the drive
using the Internal Interface (ribbon) cable.
• Apply power to the drive.
• Cycle power to the drive.
• If cycling power does not correct the
problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.
• If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
• Cycle power to the drive.
• Replace the adapter.
• Place the scanner in RUN mode.
• Program the controller to recognize and
transmit I/O to the adapter.
• Configure the adapter for the program in the
controller.
No action required.