3. In the list, select the EtherNet/IP scanner or bridge used by your
controller and then select the major revision of its firmware in the
Major Revision box. In this example
1756-ENBT EtherNet/IP Bridge (Series A), so the 1756-ENBT/A
option is selected.
4. Click OK. The Module Properties dialog box
Figure 4.4 Module Properties Dialog Box - Page 1
5. Edit the following:
Box
Name
Slot
Revision
IP Address
Electronic Keying Compatible Module. This setting for Electronic Keying
6. Click Finish>>. The scanner or bridge is now configured for the
EtherNet/IP network. It appears in the I/O Configuration folder. In
our example, a 1756-ENBT bridge appears under the I/O
Configuration folder
Figure 4.5 RSLogix 5000: I/O Configuration Folder
Configuring the Scanner or Bridge
Type
A name to identify the scanner or bridge.
The slot of the EtherNet/IP scanner or bridge in the rack.
The minor revision of the firmware in the scanner. (You
already set the major revision in the Select Module Type
dialog box,
Figure 4.3
The IP address of the EtherNet/IP scanner or bridge.
ensures the physical module is consistent with the software
configuration before the controller and scanner or bridge
make a connection. Therefore, ensure that you have set the
correct revision in this dialog box. Refer to the online Help if
the controller and scanner have problems making a
connection and you want to change this setting.
(Figure
4.5).
(Figure
4.3), we use a
(Figure
on
page
4-2.)
4-3
4.4) appears.